DAB PUMPS ACTIVE DRIVER M/M 1.1 Скачать руководство пользователя страница 16

ENGLISH

50

10.

ACCESS TO MANUAL MODE OF THE MACHINE

         

             (ref. Table no. 14 page 53)

Access keys SET and + and – for 5 seconds        

During this phase all the controls and protection systems of the ACTIVE DRIVER are 
disabled!

Use of the keys 

Keys pressed 

Action 

SET

 and + and –  Press them together for a few moments until the display shows MA 

Increases the frequency and rotation of the electropump 

– 

Decreases the frequency and rotation of the electropump 

MODE

Moves on to the next item in the following menu 
FP = 

Setting

 of the test frequency in manual mode (Hz) 

”

 at the set FS value 

UP = Display of pressure (bar) 
C1 =  Display of the electropump phase current (A) 
rt =

Setting

 of the direction of rotation 

UF = Display of flow 
ZF =  Display of zero flow 

MODE

 and – 

The electropump runs at the set frequency as long as the keys are held down 

MODE

 and – and 

+

(for 2 seconds) 

The electropump remains operating at the set frequency. 
The electropump may be switched off by pressing 

SET

 (when 

SET

 is pressed a second time 

it takes you out of the Manual Mode menu).

SET

 and – 

Changes the direction of rotation of the electropump (active only with the pump running).

SET

Press to stop the electropump or to leave manual mode.

10.1  rt : setting the direction of rotation

In manual mode, irrespective of which heading you are under, you can always invert the direction of 
rotation by simultaneously holding down the 

SET

 and – keys for 2 seconds, this command is active only 

with the pump running. 

10.2  Starting the electropump . 

Pressing the 

MODE

 and – and + keys simultaneously stops the electropump at the frequency FP. 

The running status remains until the 

SET

 key is pressed. 

When the electropump is ON the display blinks quickly. 
When the electropump is OFF the display blinks slowly. 
In manual mode, pressing the 

SET

 key takes you out of the menu, but if the electropump has been 

started, pressing the key stops only the electropump; when the electropump is stopped, pressing 

SET

takes you out of the menu.

11.

GENERAL SYSTEM RESET

                            (ref. Table no. 14 page 53)

Access keys MODE and SET and + and –  

To restart the appliance without disconnecting the power supply press the 4 keys simultaneously. 

MODE and SET and + and – 

12.

RESTORING THE FACTORY SETTINGS                                    (ref. Table no. 14 page 53)

Access keys SET and +  
for 2 seconds when switching on 

The factory settings are indicated in table no. 14 on page 53. 
To reset the factory values: 
Switch off the appliance, press and hold down the 

SET

and

+

 keys while switching on the appliance again, 

release the two keys only when the letters EE appear. In this case the ACTIVE DRIVER restores the factory 
settings. When it has finished setting all the parameters the ACTIVE DRIVER returns to normal operation.

In this phase, in the models in which RC is active, the motor current is set at 0 as factory 
default, so when you try to start the electropump it will immediately give the error EC.   Go to 
the installer’s display and settings menu (keys MODE and SET and – for 5 seconds ) and set the 
correct motor data plate current (parameter rC as in paragraph 8.5.1.)

13.

ERROR AND STATUS CONDITIONS                                            (ref. Table no. 14 page 53)

The ACTIVE DRIVER is equipped with protection systems to preserve the pump, the motor, the 
supply line and the ACTIVE DRIVER itself. 

If one or more protections trip, the one with the highest priority is immediately notified on the display. 
Depending on the type of error the electropump may switch itself off, but when normal conditions are restored 
the error status may be cancelled immediately or only after a certain time, following an automatic reset.

Содержание ACTIVE DRIVER M/M 1.1

Страница 1: ...ifications KONFORMIT TSERKL RUNG Die Firma DAB PUMPS s p a Via M Polo 14 Mestrino PD ITALIEN erkl rt eigenverantwortlich dass die vorstehend beschriebenen Produkte den folgenden Richtlinien entspreche...

Страница 2: ...SENIE O ZHODE Spolo nos DAB PUMPS s p a Via M Polo 14 Mestrino PD Taliansko vyhlasuje na vlastn v hradn zodpovednos e v robky uveden v d al om texte zodpovedaj Smernici Elektromagnetick kompatibilita...

Страница 3: ...nd SET and keys for 5 seconds 46 8 6 1 tb Setting the reaction time of the water lack blockage 46 8 6 2 GP Setting the gain of the proportional coefficient of the PI 46 8 6 3 GI Setting the gain of th...

Страница 4: ...ircuit between the phases of the output terminal 52 13 6 Manual reset of error conditions 52 13 7 Self reset of error conditions 52 14 INDICATIONS ON THE DISPLAY 53 INDEX OF TABLES Page Table 4 Techni...

Страница 5: ...Manufacturer declines all responsibility for possible errors in this instructions manual if due to misprints or errors in copying The Manufacturer reserves the right to make any modifications to produ...

Страница 6: ...rth terminal 5 2 Check that all the connecting cables are in excellent conditions with the external sheathing unbroken 5 3 The motor of the installed electropump must comply with the data in the table...

Страница 7: ...is operative it is absolutely necessary to protect it suitably against frost and to leave it constantly fed If it is disconnected from the power supply the anti frost function is no longer active If t...

Страница 8: ...excluding A D M M 1 1 and A D M T 1 0 250 Vac 6 A max resistive load 3 A max inductive load J14 o2 Pump operating connection terminal excluding A D M M 1 1 and A D M T 1 0 250 Vac 6 A max resistive l...

Страница 9: ...regulating pressure becomes P1 switch over active setpoint SP or P1 Example Use IN 3 When IN 3 is activated the pump is blocked and the signal F3 is given ex IN 3 could be connected to a safety pressu...

Страница 10: ...a plate of the electropump motor If the set parameter is lower than the correct one during operation the error message oC will appear as soon as the set current has been exceeded for a certain time If...

Страница 11: ...ng status 8 5 1 rC Setting the rated current of the electropump excluding A D M M 1 1 This parameter must be set the same as the current on the motor data plate Amps in the configuration in which it i...

Страница 12: ...CTIVE DRIVER on each of the two machines 8 5 7 Eb Enable booster pre set value 2 excluding A D M M 1 1 When two ACTIVE DRIVER units are interconnected with each other in the case where only one ACTIVE...

Страница 13: ...with Fn whenever a new Fn is set 8 6 6 Ft Setting the low flow rate threshold The ACTIVE DRIVER system possesses a flow sensor Whenever the electropump is switched off a new zero is acquired The ACTI...

Страница 14: ...ump has to be started for the time St The pre set value is 45 Hz and it may be varied between Fn and Fn 50 using the and keys If a FL higher than Fn 50 has been set SF will be limited to the value of...

Страница 15: ...le no 14 page 53 Access keys SET and for 2 seconds From normal operating status pressing the key SET and enters the MONITOR function where the following values are displayed NB to scroll through the v...

Страница 16: ...nks quickly When the electropump is OFF the display blinks slowly In manual mode pressing the SET key takes you out of the menu but if the electropump has been started pressing the key stops only the...

Страница 17: ...ion Description bL Blockage due to water lack bP Blockage due to absence of pressure sensor LP Blockage due to low supply voltage HP Blockage due to high rectified voltage ot Blockage due to overheati...

Страница 18: ...enever a short circuit occurs an event counter is increased and saved in the permanent memory EEPROM AFTER THE HUNDREDTH SHORT CIRCUIT THE MACHINE BLOCKS PERMANENTLY AND IT WILL NO LONGER BE POSSIBLE...

Страница 19: ...flow rate threshold 15 15 15 15 15 CM Exchange method on sets of 2 electropumps 01 01 01 01 AE Setting the enabling of the anti block anti frost function 01 01 01 01 01 SF Setting the starting freque...

Страница 20: ...e sensor LP Blockage due to low supply voltage HP Blockage due to high supply voltage ot Blockage due to overheating of the power stages oC Blockage due to current overload in the electropump motor oF...

Страница 21: ...6 Ad A D M M 1 1 136 8 5 7 Eb booster 2 A D M M 1 1 136 8 6 MODE SET 5 136 8 6 1 tb 136 8 6 2 GP PI 136 8 6 3 GI PI 137 8 6 4 FS 137 8 6 5 FL 137 8 6 6 Ft 137 8 6 7 CM 1 A D M M 1 1 137 8 6 8 AE 137...

Страница 22: ...2 140 11 RESET MODE SET 140 12 SET 140 13 140 13 1 bL 141 13 2 bP 141 13 3 LP A D M M 1 1 A D M T 1 0 142 13 4 oF ot 45 C 142 13 5 SC 142 13 6 reset 142 13 7 142 14 143 4 130 8 1 131 8 2 134 8 6 12 IN...

Страница 23: ...9 1 2 2 1 IEC 60634 2 2 CEI 64 2 2 3 ACTIVE DRIVER 2 4 IEC 536 1 NEC U V W Active Driver M M 1 1 R S EN 60204 9 2 5 4 3 ACTIVE DRIVER ACTIVE DRIVER M T 230V ACTIVE DRIVER M M 230V ACTIVE DRIVER T T 40...

Страница 24: ...r 16 bar 16 bar 16 bar 16 bar 1 6 bar 1 9 bar 1 15 bar 1 15 bar 1 15 bar x x 22x28x18 cm 22x28x18 cm 22x28x18 cm 22x28x18 cm 22x28x18 cm 1 1 1 1 1 1 1 1 1 1 IP 55 IP 55 IP 55 IP 55 IP 55 A D M M A D M...

Страница 25: ...RIVER ACTIVE DRIVER 7 2 ACTIVE DRIVER 7 3 ACTIVE DRIVER 7 4 ACTIVE DRIVER 0 C ACTIVE DRIVER ACTIVE DRIVER 8 ACTIVE DRIVER ACTIVE DRIVER inverter M M 1 1 M T 1 0 ACTIVE DRIVER 3 2 1 2 3 2 ACTIVE DRIVER...

Страница 26: ...I3 I2 A D M M 1 1 A D M T 1 0 6 IN 1 i1 A D M M 1 1 A D M T 1 0 J22 7 0V DC GND A D M M 1 1 A D M T 1 0 o1 A D M M 1 1 A D M T 1 0 250 Vac 6 A 3 A J14 o2 A D M M 1 1 A D M T 1 0 250 Vac 6 A 3 A J9 1...

Страница 27: ...N 1 F1 IN 1 IN 2 IN 2 P1 set point SP P1 IN 3 IN 3 F3 IN 3 Max 48V Max 50Vrms Max 48V Max 50Vrms Max 48V Max 50Vrms 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 AC DC 1 2 3 4 5 6 7 AC DC 1...

Страница 28: ...MODE SET SET 6 6 SET SET 8 3 ACTIVE DRIVER 14 143 ACTIVE DRIVER ZF EC ACTIVE DRIVER Hz 8 3 1 rC MODE SET rC oC SET Fn ACTIVE DRIVER EC 8 3 2 Fn rC MODE Fn Fn MODE SET ACTIVE DRIVER 8 3 3 Fn MODE rt AC...

Страница 29: ...M 1 1 1 9 bar A D M T 1 0 1 15 bar SET ACTIVE DRIVER RP bar SP 8 5 14 143 MODE SET 5 SET MODE SET rC MODE set 8 5 1 rC A D M M 1 1 Ampere 230V A D M T 400V A D T T 8 5 2 rt A D M M 1 1 0 1 Fr MODE GO...

Страница 30: ...der ACTIVE DRIVER Ad Ad ACTIVE DRIVER Go Sb Ad ACTIVE DRIVER ACTIVE DRIVER SP setpoint rP Eb booster CM M dP P1 set point P1 2 ACTIVE DRIVER 8 5 7 Eb booster 2 A D M M 1 1 ACTIVE DRIVER ACTIVE DRIVER...

Страница 31: ...Ft ACTIVE DRIVER ACTIVE DRIVER 0 ZF Ft 8 6 7 CM 1 A D M M 1 1 ACTIVE DRIVER CM 0 ACTIVE DRIVER leader ACTIVE DRIVER booster Eb 2 Eb 1 23 leader leader booster Eb 2 leader ACTIVE DRIVER booster leader...

Страница 32: ...11 St St SF PI St 1 St 0 3 8 6 12 IN1 IN2 IN3 i1 i2 i3 A D M M 1 1 A D M T 1 0 IN1 IN2 IN3 i1 i2 i3 i1 i2 i3 0 1 3 2 3 i3 3 4 5 IN1 IN2 IN3 0 1 2 3 4 5 F1 i1 F1 IN1 Set point P1 IN1 set point P1 i2 F2...

Страница 33: ...t point SP P1 1 9 bar 8 6 14 O1 1 A D M M 1 1 A D M T 1 0 O2 2 A D M M 1 1 A D M T 1 0 OUT1 OUT2 0 1 2 3 o1 o2 9 9 1 14 143 MODE MODE Fr Hz UP bar C1 A A D M M 1 1 A D M T 1 0 UE 9 2 SET 2 SET MONITOR...

Страница 34: ...FS UP bar C1 A rt UF ZF MODE MODE 2 SET SET SET SET 10 1 rt SET 2 10 2 MODE FP SET SET SET 11 RESET 14 143 MODE SET 4 MODE SET 12 14 143 SET 2 14 143 SET EE ACTIVE DRIVER ACTIVE DRIVER RC 0 EC MODE S...

Страница 35: ...141 bL oC oF SC FS FS 20 Fr Lt LC Lb bL bP LP HP ot ob oC oF oF ot 45 C SC EC rC Fn E0 E7 0 7 F1 1 F3 3 13 1 bL setpoint bL 2 3 13 2 bP ACTIVE DRIVER bP 10...

Страница 36: ...A D M T 1 0 180V ACTIVE DRIVER 200V 13 4 oF ot 45 C oF ot 45 C 2 13 5 SC ACTIVE DRIVER U V W PUMP 10 EEPROM 13 6 RESET 13 7 ACTIVE DRIVER bL 10 6 1 24 24 30 bP 10 LP 220V 20 10 HP Ot 70 C OC 10 6 oF 1...

Страница 37: ...ar 0 5 bar Ad Eb booster 02 02 02 02 MODE SET 5 tb s 10 s 10 s 10 s 10 s 10 s GP PI 1 0 1 0 1 0 1 0 1 0 GI PI 1 0 1 0 1 0 1 0 1 0 FS Hz 50 50 50 50 50 FL Hz 0 0 0 0 0 Ft 15 15 15 15 15 CM 2 01 01 01 0...

Страница 38: ...144 14 Reset MODE SET A D M M 1 1 A D M T 1 0 A D M T 2 2 A D T T 3 0 A D T T 5 5 ZF ZF SET 2 EE EEprom bL bP LP HP ot oC oF oF ot 45 C SC EC rC Fn E0 E7 0 7 F1 1 F3 3...

Отзывы: