Main closing edge
Beside closing edge
Beside -
closing edge
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing ranges C3 and C2, the drive
runs "OPEN" for 10 seconds, then "CLOSE" again. If
closing is not possible after three attempts, the drive
remains in this position.
In addition, the drive is equipped with passive
protection. The closing speed in closing range C2
and C1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
C3*
200 N
Opening and Closing Ranges
O1*
C1*
C2*
O2*
O3*
23 mm
150 N
77 mm
150 N
23 mm
200 N
15 mm
200 N
200 N
Technical Data
* Programmable with software SCS ** + approx. 20 % switch-off reserve (temporary)
Type
VCD-0204-0250-5-ACB
VCD-0204-0350-5-ACB
Power supply
Nominal force
Input power
230 V AC, +10 % / -15 %, 50 Hz
200 N**
22 W / 30 VA
Nominal stroke length*
250 mm
±
2 %
350 mm
±
2 %
Running speed:
O1, O2
O3
C3
C2, C1
6 mm/s
5 mm/s
6 mm/s
5 mm/s
Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temp. range
Ambient humidity
Emission sound pressure level
Additional functions*
approx. 2000 N (Excluding bracket)
>20.000 double strokes
30 % (With cycle time 10 minutes)
Zinc-diecasting powdercoated (~ RAL 9006)
IP 30
0 ... +60 °C
≤ 90 %, not condensing
LpA ≤ 46 dB(A)
Closing edge protection = activated (3 repetitions of stroke);
Locking relief = activated (retraction lift max. 0,2 mm)
ACB interface
Modbus RTU / RS 485, 19.200 bps, 8 data bits, 1 stop bit, parity: even
- At vertical active pulling application (e.g. for a
skylight) the forces must be rearranged by
software SCS.
- If after mounting, the distance X is greater than
23 mm, null balance with software SCS is
neccesary. Closure Ranges will shift in relation to
new zero point.
Mounting information
ACB interface
ACB is used for secure communication between
the drive and compatible D+H control systems. It
enables activation, diagnostics and configuration
with perfect position, directly from the control
panel. In this process, all status messages, such
as the OPEN and CLOSED signals, opening
stroke and drive errors, are transmitted to the
control panel.
The ACB bus is based on an open Modbus RTU
protocol via which the actuator can be directly
controlled and queried.
Further information can be found in the D+H ACB
Planning Manual.
Functional description
≥ 23 mm ?
X
VCD 204-5-ACB-M
VCD 204-5-ACB-M
Wiring:
Is the drive wired properly?
See connection plans.
Diagnostics with SCS software:
The SCS software and a BSY+ interface is
required for further troubleshooting or
configuration.
Troubleshooting