background image

1. There is no power applied
2. The UCM Firmware programming cable is connected to PP1. This cable should be

connected between UCM05 and PP1 only for firmware upgrade operation. The cable can

be left connected to PP1 in normal operation only if it is not connected to the UCM at

the same time.

3. The 12V supply is shorted by external devices or wiring and  heatsink is hot (see next

item)

System does not work, and Heatsink is very hot

This is probably due to a short on one of the wires connected to the system or an external

device drawing too much current, causing the  power supply to shut down to protect itself.

Unplug all the terminal blocks from inputs, outputs. 12V auxiliary out, keypads  and other

terminals. It may be necessary to switch off and leave the power off for several minutes to

allow the resettable fuses to  cool down and reset. Check the correct sequence of red and

green leds as described above when the power is switched on Then connect one keypad and

other devices one by one. This will help discover the cause of the short or excessive current

Communications Failure

The keypad Home LED blinks and “Communication Failure,

ID

“ followed by the ID number

is reported upon user sign-in. This  means that a slave device, ie Keypad, Door Station,

SEM, UCM, or RIO/SCS is not communicating with the Comfort panel. The ID address of the

device which is not communicating is reported. This ID  identifies which device is giving the

problem, according to the table below”

88

8

72

8

87

7

71

7

86

6

70

6

85

5

69

5

84

4

68

4

83

3

67

3

82

2

66

2

81

1

65

1

ID

RIO/SCS

ID

Keypad

51

3

24

8

50

2

23

7

49

1

22

6

ID

Door Station

21

5

20

4

35

3

19

3

34

2

18

2

33

1

Not Reported

1

ID

SEM (Slave)

ID

UCM

The name of device causing the communications failure is displayed on the KP04 LCD

keypad

1

Check the wiring to the unit concerned.

2

If Communications Failure happens each time on Security Off, the power to the device

may have been connected to  S12V. Power to the devices should be connected to 12V

terminals, except in the case of SEM01 which have their own power supply.

3

The problem could also be due to one of the devices on the RS485 bus (eg SEM,

Keypad, Door Station, UCM) putting a fault on the bus. Remove each device from the

KA/KB line and see if the communications failure problem disappears.

Comfort II Supplementary Installation Manual

14

Содержание Ultra Comfort II

Страница 1: ...Comfort II Supplementary Installation Manual Comfort the Intelligent Home System...

Страница 2: ...THE PRINTED MANUAL MAY NOT BE THE LATEST VERSION ALWAYS CHECK WWW CYTECH BIZ FOR THE UPDATED VERSION OF THIS MANUAL...

Страница 3: ...LEDs both remain on 13 The Green LED does not blink once after Reset 13 Startup Problems 13 Troubleshooting Kit 13 Section 3 Troubleshooting 12 Remember to set Time and Date 12 Door Station 12 Voice...

Страница 4: ...Comfort II Supplementary Installation Manual 1...

Страница 5: ...atery charger with built in protection against deep discharge of battery shuts down system when battery falls below a threshold preventing damage to the battery Current limited 400 mA battery charging...

Страница 6: ...protected outputs X10 Compatibility Built in two way interface to X10 network via PSC05 110V 60 Hz TW7223 or XM10E 230V 50 Hz module X10 modules not supplied Keypad Door Station Up to 8 Keypads and 3...

Страница 7: ...Test Momentary activation Strobe Test turns on and off the strobe Engineer Test Mode allows engineer to work on the system without triggering tamper or 24 hour alarms Event Log Event Log accessible by...

Страница 8: ...12 V lamps for testing RLY02 8 8 way Reed Relay Module CSM03 PCB Dual Current Sensor PCB supports 2 CSM03 CT sensors CSM03 CT Current Transformer 2 CSM03 CT are connected to 1 CSM03 PCB RC01 YE Yellow...

Страница 9: ...als like presentations tutorials exercises etc which are updated from time to time For Users User Manual with Quick Start Guide The Quick Start Guide gives simple instructions on how to get started wi...

Страница 10: ...es Yes Local Phone Control Yes Yes Remote Phone Access 16 16 User Sign in Codes Yes Yes Sunrise Sunset Daylight saving 16 32 Time Programs 8 16 Reminder Messages Yes Yes Extended X10 codes Send 1 16 R...

Страница 11: ...s with dedicated Tamper Input and Siren Strobe and Speaker outputs A Local Expansion Module provides another 8 inputs and 8 outputs LEM01 or 8 inputs LEM02 in the same enclosure to give a maximum of 1...

Страница 12: ...re cable as well you never know what may be needed in the future If possible use screened cables for trouble free installations Current Consumption It is very easy to underestimate the load which can...

Страница 13: ...r lighting the same external PIRs could be used to operate lighting The prevailing light level can be determined by using a photocell connected to a zone and the corresponding light turned on if it is...

Страница 14: ...The Speaker and Keypad should give a slow beeping tone and any programmed Entry Alert Response should be activated Entry path zones should be announced but not cause an alarm Sign in to disarm to Sec...

Страница 15: ...t the various menus Each key pressed should be followed by a beep tone to show that the key has been recognized Voice Station 1 If there are more than 1 Keypad press F 8 to activate Intercom mode All...

Страница 16: ...efer to the Indicator LEDs table in the previous section The correct sequence should be 1 Both Leds turn on 2 The Red LED goes off after 1 second with the green LED remaining on 3 The Green LED turns...

Страница 17: ...unications Failure The keypad Home LED blinks and Communication Failure ID followed by the ID number is reported upon user sign in This means that a slave device ie Keypad Door Station SEM UCM or RIO...

Страница 18: ...table in Chapter 2 3 Check that the Number of Keypads Location 1675 and Number of Door Stations Location 1674 are correctly set to the number of keypads and Door Stations respectively The Comfort syst...

Страница 19: ...Station or Door Station In Voice Station or Door Station mode if you cannot hear sounds on the keypad or Door Station even if you keep silent i e cannot switch to Listen Mode but the KP or Door Stati...

Страница 20: ...Telephone Line This is usually due to the telephone wiring or a fault on the incoming telephone line Switch off Comfort at the mains and disconnect the battery In this condition the telephone line is...

Страница 21: ...a loss of security as the System is unable to dial out if the parallel phone is offhook This cannot be used for UL systems or monitored systems and is meant for systems concerned mainly with Home Aut...

Страница 22: ...reporting to be aborted as Comfort thinks the phone is offhook The telephone may otherwise seem to be working properly able to make and receive calls System Cannot Dial Out 1 Check that J3 header is...

Страница 23: ...the system must be disarmed before it can be armed again Any attempt to arm when there is an alarm active will result in he message Call Engineer to Reset When arming the keypad beeps rapidly but no Z...

Страница 24: ...their code it will be preceded by time mailbox sign in code OK N A Duress Alarm Doorbell pressed while system is armed N A Doorbell System dial test selected N A Dial Test The system is armed to Day...

Страница 25: ...om Monitoring Station received N A Monitoring Station OK Valid user code 1 16 entered remotely using external phone N A Name Phone Call Sign In Valid user code 1 16 entered using local phone or Keypad...

Страница 26: ...ring a Battery Test F3 1 or the Scheduled Daily Battery Test Configuration Modules Settings Misc Settings Comfort switches off the AC power to the system during the battery test and if the battery vol...

Страница 27: ...phone is used a Phone Trouble alarm will be reported To disable telephone line cut detection refer to Worksheet Table 35 for Location 40 settings One of the settings add 2 is to ignore Line cut After...

Страница 28: ...ber This product must be installed in accordance with the installation instructions contained in this manual CE Marking Europe This equipment complies with the requirements of the EMC Directive 89 336...

Страница 29: ...rt numbers and APB01 3 1 2 6 September 2008 Revised Siren Bellbox Backup Battery Troubleshooting section Rewrite of Quick Start Power On Checklist Added Indicator LEDs Table 3 1 0 21 October 2007 Used...

Страница 30: ...Comfort II Supplementary Installation Manual 27...

Страница 31: ...Comfort II Supplementary Installation Manual 28...

Страница 32: ...ng Fit to Printable Area Select Properties Finishing Tab Document Options Print on Both Sides Booklet Layout Left Side Binding Other printers may have different settings to achieve the same result Com...

Отзывы: