Door Station cannot Ring the Telephone

If pressing the Door station button cannot ring the local telephone, but the keypad can

answer the door station, the problem could be in the Ringer Module. Check that the ringer

cable from the Ringer Module to Comfort main PCB is connected correctly.
The problem could also be caused by a telephone or too many telephones connected in

parallel. The Ringer cannot drive an unlimited number of telephones. See

Too many

Telephone/Faulty Telephones

 below.

Doorbell Chime is too loud

Remove the shunt from header JP6  on the DP03 PCB to soften the doorbell chime.

No Voice on Keypads or Telephones

If there is no voice menu heard on the keypads, use the local phone to sign in by pressing

* and user code and the # key. If the voice menu is not heard, then the voice may be

corrupted. The system still operates normally and  can be armed and disarmed except that

the announcements cannot be heard. Intercom mode and recording and functions which do

not depend on the words and sentences can still work, This has been known to occur in

some systems due to unknown reasons which are being investigated. To restore the voice,

use Comfigurator to do a Vocabulary Download, selecting the voice file kate28.bin for

English. The UCM05 is required for this. If you are uncertain about which voice file to use,

contact [email protected]. The Vocab Upgrade takes more than 20 minutes.

Voice Station/Door Station Intercom Problems

There is a Comfort II Tuning Parameter Adjustment Guide on the Cytech web site on the

Technical Info page. This gives instructions on how to adjust the tuning parameters to solve

many common intercom problems

Telephone cannot hear Voice Station or Door Station

In Voice Station or Door Station mode, if  you cannot hear sounds on the keypad or Door

Station even if you keep silent, (i.e.. cannot switch to Listen Mode), but the KP or Door

Station is able to hear the telephone, try the following steps:

1

Does the problem occur only for 1 unit (keypad or Door Station)? If so it is a problem

with the wiring of the MIC wire from the affected Keypad or Door Station, or a faulty

microphone on the unit. You can check the MIC and Speaker on all keypads by using

the Keypad Intercom mode (F+8). Check that all other keypads can hear. Press a key

on other keypads to put that keypad into talk mode and check that the  microphone on

that unit is working.

2

Too much background noise around the telephone can prevent the keypad or door

station from being heard.  Try moving to a quieter area.

Door Station or Keypad cannot hear voice from telephone

The converse of the previous problem is the telephone voice cannot be heard on the keypad

or door station, but the keypad/Door station voice can be heard on the telephone.  Try the

following steps:

1

If only 1 Keypad or Door Station is unable to hear the telephone voice, the volume

control on the keypad or Door Station may be set too low. The SPK wire on the affected

unit may be not connected properly, or the speaker may be faulty. A noisy

environment around one of the units may also prevent the telephone from getting

through.

2

If all the keypad/door stations are not able to hear voice coming from the telephone,

check “Phone Intercom Voice Level” in Comfigurator > Voice Settings. This can also be

programmed in Location 1700. This sets the  gain level of the voice from the telephone

to the speakers. The values range from 0 (minimum) to 3 (maximum). Any value

higher than 3 is taken to be 3 (maximum). Reset is not required. The default level is 2.

Comfort II Supplementary Installation Manual

16

Содержание Ultra Comfort II

Страница 1: ...Comfort II Supplementary Installation Manual Comfort the Intelligent Home System...

Страница 2: ...THE PRINTED MANUAL MAY NOT BE THE LATEST VERSION ALWAYS CHECK WWW CYTECH BIZ FOR THE UPDATED VERSION OF THIS MANUAL...

Страница 3: ...LEDs both remain on 13 The Green LED does not blink once after Reset 13 Startup Problems 13 Troubleshooting Kit 13 Section 3 Troubleshooting 12 Remember to set Time and Date 12 Door Station 12 Voice...

Страница 4: ...Comfort II Supplementary Installation Manual 1...

Страница 5: ...atery charger with built in protection against deep discharge of battery shuts down system when battery falls below a threshold preventing damage to the battery Current limited 400 mA battery charging...

Страница 6: ...protected outputs X10 Compatibility Built in two way interface to X10 network via PSC05 110V 60 Hz TW7223 or XM10E 230V 50 Hz module X10 modules not supplied Keypad Door Station Up to 8 Keypads and 3...

Страница 7: ...Test Momentary activation Strobe Test turns on and off the strobe Engineer Test Mode allows engineer to work on the system without triggering tamper or 24 hour alarms Event Log Event Log accessible by...

Страница 8: ...12 V lamps for testing RLY02 8 8 way Reed Relay Module CSM03 PCB Dual Current Sensor PCB supports 2 CSM03 CT sensors CSM03 CT Current Transformer 2 CSM03 CT are connected to 1 CSM03 PCB RC01 YE Yellow...

Страница 9: ...als like presentations tutorials exercises etc which are updated from time to time For Users User Manual with Quick Start Guide The Quick Start Guide gives simple instructions on how to get started wi...

Страница 10: ...es Yes Local Phone Control Yes Yes Remote Phone Access 16 16 User Sign in Codes Yes Yes Sunrise Sunset Daylight saving 16 32 Time Programs 8 16 Reminder Messages Yes Yes Extended X10 codes Send 1 16 R...

Страница 11: ...s with dedicated Tamper Input and Siren Strobe and Speaker outputs A Local Expansion Module provides another 8 inputs and 8 outputs LEM01 or 8 inputs LEM02 in the same enclosure to give a maximum of 1...

Страница 12: ...re cable as well you never know what may be needed in the future If possible use screened cables for trouble free installations Current Consumption It is very easy to underestimate the load which can...

Страница 13: ...r lighting the same external PIRs could be used to operate lighting The prevailing light level can be determined by using a photocell connected to a zone and the corresponding light turned on if it is...

Страница 14: ...The Speaker and Keypad should give a slow beeping tone and any programmed Entry Alert Response should be activated Entry path zones should be announced but not cause an alarm Sign in to disarm to Sec...

Страница 15: ...t the various menus Each key pressed should be followed by a beep tone to show that the key has been recognized Voice Station 1 If there are more than 1 Keypad press F 8 to activate Intercom mode All...

Страница 16: ...efer to the Indicator LEDs table in the previous section The correct sequence should be 1 Both Leds turn on 2 The Red LED goes off after 1 second with the green LED remaining on 3 The Green LED turns...

Страница 17: ...unications Failure The keypad Home LED blinks and Communication Failure ID followed by the ID number is reported upon user sign in This means that a slave device ie Keypad Door Station SEM UCM or RIO...

Страница 18: ...table in Chapter 2 3 Check that the Number of Keypads Location 1675 and Number of Door Stations Location 1674 are correctly set to the number of keypads and Door Stations respectively The Comfort syst...

Страница 19: ...Station or Door Station In Voice Station or Door Station mode if you cannot hear sounds on the keypad or Door Station even if you keep silent i e cannot switch to Listen Mode but the KP or Door Stati...

Страница 20: ...Telephone Line This is usually due to the telephone wiring or a fault on the incoming telephone line Switch off Comfort at the mains and disconnect the battery In this condition the telephone line is...

Страница 21: ...a loss of security as the System is unable to dial out if the parallel phone is offhook This cannot be used for UL systems or monitored systems and is meant for systems concerned mainly with Home Aut...

Страница 22: ...reporting to be aborted as Comfort thinks the phone is offhook The telephone may otherwise seem to be working properly able to make and receive calls System Cannot Dial Out 1 Check that J3 header is...

Страница 23: ...the system must be disarmed before it can be armed again Any attempt to arm when there is an alarm active will result in he message Call Engineer to Reset When arming the keypad beeps rapidly but no Z...

Страница 24: ...their code it will be preceded by time mailbox sign in code OK N A Duress Alarm Doorbell pressed while system is armed N A Doorbell System dial test selected N A Dial Test The system is armed to Day...

Страница 25: ...om Monitoring Station received N A Monitoring Station OK Valid user code 1 16 entered remotely using external phone N A Name Phone Call Sign In Valid user code 1 16 entered using local phone or Keypad...

Страница 26: ...ring a Battery Test F3 1 or the Scheduled Daily Battery Test Configuration Modules Settings Misc Settings Comfort switches off the AC power to the system during the battery test and if the battery vol...

Страница 27: ...phone is used a Phone Trouble alarm will be reported To disable telephone line cut detection refer to Worksheet Table 35 for Location 40 settings One of the settings add 2 is to ignore Line cut After...

Страница 28: ...ber This product must be installed in accordance with the installation instructions contained in this manual CE Marking Europe This equipment complies with the requirements of the EMC Directive 89 336...

Страница 29: ...rt numbers and APB01 3 1 2 6 September 2008 Revised Siren Bellbox Backup Battery Troubleshooting section Rewrite of Quick Start Power On Checklist Added Indicator LEDs Table 3 1 0 21 October 2007 Used...

Страница 30: ...Comfort II Supplementary Installation Manual 27...

Страница 31: ...Comfort II Supplementary Installation Manual 28...

Страница 32: ...ng Fit to Printable Area Select Properties Finishing Tab Document Options Print on Both Sides Booklet Layout Left Side Binding Other printers may have different settings to achieve the same result Com...

Отзывы: