Indicators:
Each Suprex unit is equipped with 2 leds to convey the operational status of the unit.
Green power LED:
This led will illuminate a continuous green color when power is applied to the unit. If this led is
not illuminated, power has been lost to the unit.
When communication is lost the Amber LED will flash slower at about 1-2 times per second.
BiColor diagnostic LED:
This led will indicate basic status of the units. If the units are not in communication with each
other the diagnostic LED will light a solid red color. When the units are able to communicate with
each other, the diagnostic LED will flash green on and off about twice per second.
INDICATORS AND SETTINGS
DIP Switch Settings:
The Cypress Suprex supports multiple reader data formats. Each data format can be set with the
dipswitch. The dip switch format will be read each time the unit powers up.
Mode 0 . Wiegand mode: Supports Wiegand data 24 to 248 bits. This mode will filter out data
(noise) of less than 24 bits.
Mode 1. Wiegand mode without filter: This mode permits all Wiegand bits to be read without
applying a noise filter. Any number of Wiegand bits from 4 to 248 will pass in this mode. Use
this mode to support equipment that uses a nonstandard number of less than 24 bits.
Mode 2. Strobed data mode, Rising edge trigger. Mercury MR-5™ reader emulation.
Mode 3. Strobed data mode, Rising edge trigger. Dorado 644™ reader emulation.
Mode 4. Strobed data mode, Rising edge trigger. Mag-Tek ™ reader emulation
Mode 5. Strobed data mode, Falling edge trigger. For all readers that trigger data on the falling
clock edge.
Mode 7. Unsupervised F/2F mode, will work with most Casi-Rusco™ F/2F format readers in
unsupervised mode.