Suprex Remote Unit Dip Switch Settings
All Off except 6,7,8 (see below for details)
Suprex Central Unit Dip Switch Settings
Switch #5- Off = (Default) Normal operation. Strike follows LED status.
On = Strike relay does NOT follow LED
General Description and specifications:
The SPX-1200 will connect a Wiegand, MagStripe, or F/2F interface reader to a compatible panel
using a single pair of wires. There is also the ability to send additional signals such as Request to Exit,
Tamper, Alarm, and Door contacts over the same communication link.
An SPX-1200 system consists of a pair of units. A
Central
unit connects to the Access Control Panel
and a
Remote
unit connects to the Badge reader and door/ gate hardware. The reader data and status
signals are sent over a single pair of wires up to 10,000 feet. An RS-232 connection can also be used.
The SPX-1200 series has the ability to be field configured for various reader formats.
Dip Switch Settings 6.7.8 for Central AND Remote
Switches 6,7,8 select the type of reader format used.
Mode 0. 6,7,8 OFF = Standard Wiegand
Mode 1. 6,7 OFF ; 8 ON = Wiegand without filtering, Use for keypads with burst transmit.
Mode 2. 6 OFF, 7 ON, 8 OFF = Strobed, rising edge trigger, (MR-5™ Compatible)
Mode 3. 6 OFF, 7 ON, 8 ON = Strobed, rising edge trigger, (Dorado 644™compatible)
Mode 4. 6 ON, 7 OFF, 8 OFF = Strobed,rising edge trigger, (Mag-Tek™ compatible)
Mode 5 6 ON, 7 OFF, 8 ON = Strobed, falling edge trigger
Mode 7 6 ON, 7 ON, 8 ON = Unsupervised F/2F (Casi-Rusco Compatible)
Switch #4- Off = Enable Internal Pullup Resistors.
On = Disable Internal Pullup Resistors.
Switch #3- Off = Normal Operation.
On = Alternate Relay Setting.