26
CY3274 Cypress High Voltage Programmable PLC Development Kit Guide, Doc. # 001-53598 Rev. *G
Kit Operation and PLC Control Panel GUI
Figure 3-4. Opening PLC20_FW_5.8.hex
5. If the board is powered, then set Programming Mode to Reset in the Programming Parameters
section. If the board is not powered, set Programming Mode to Power Cycle. Then, set
Verification to Off (faster programming times, checksum still performed) and AutoDetection to On.
6. Click the Program Part button. The status window should show Programming Starting. If it does
not, make sure that the Programming Mode is set correctly (see step 5) and the MiniProg is
connected to the ISSP connector on the PLC board (see the kit user guide for location of the
connector). If set up correctly, the status window shows Programming Succeeded in less than a
minute.
Figure 3-5. PSoC Programmer
7. Remove the MiniProg from the ISSP header and press the RESET push-button on the PLC.
8. Follow the steps 1 to 7 on another PCL node.