Circuit Breaker Trip Time
Depending on the model, the AlterPath PM uses either one 10 amp, one 20
amp, two 15 amp, or two 16 amp circuit breakers. The following table shows
the circuit breaker trip time for all PM models.
Table C-20:
Circuit Breaker Trip Time
Current Load
Trip Time
200%
5-30 seconds
300%
1.8-10 seconds
400%
0.9-5 seconds
500%
0.5-3.3 seconds
600%
0.38-2.3 seconds
800%
0.2-1.3 seconds
1000%
0.15-0.9 seconds