![CyberPower RMCARD205 Скачать руководство пользователя страница 57](http://html1.mh-extra.com/html/cyberpower/rmcard205/rmcard205_user-manual_2702133057.webp)
CyberPower Remote Management System
55
A
ppendix 2:
How to Configure a RMCARD User
Account in Authentication Servers
RADIUS
1. Add a new attribute to RADIUS Dictionary as the Cyber vendor:
3808
– Vendor
2. Add two new specific attributes to RADIUS server interface under the vendor:
(1)
Cyber-Service-Type
(integer variable)
Cyber-Service-Type can accept three integer parameter values:
1
– Administrator
2
– Viewer
3
– Outlet User
(2)
Cyber-Outlets
(string variable)
Cyber-Outlets can accept a string describing outlet numbers. This attribute will let the outlet user
access and control the designated outlets. For example, Cyber-Outlets=
“1,2,5” allows the user to
control outlets 1, 2 and 5.
The example of the Dictionary File:
VENDOR Cyber 3808
BEGIN-VENDOR Cyber
ATTRIBUTE Cyber-Service-Type 1 integer
ATTRIBUTE Cyber-Outlet 2 string
VALUE Cyber-Service-Type Admin 1
VALUE Cyber-Service-Type Viewer 2
VALUE Cyber-Service-Type Outlet 3
END-VENDOR Cyber
LDAP & Windows AD
Add one of the attributes below to
description
on the OpenLDAP or Windows AD interface for
indicating the user account type and authentication:
1.
cyber_admin
(Administrator)
2.
cyber_viewer
(Viewer)
3.
cyber_outlet=
“string”
(Outlet user)
The string entered in cyber_outlet designates what outlets the Outlet User can access and control.
For example, cyber_outlet=
“1,2,5” allows the user to control outlets 1, 2 and 5.