![CyberPower RMCARD205 Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/cyberpower/rmcard205/rmcard205_user-manual_2702133037.webp)
CyberPower Remote Management System
35
Example 4:
To set On-line UPS mode to generator mode
CyberPower >
upscfg mode generator
upsbatt
Description: Show information of battery, and execute the battery test and battery runtime calibration.
Option
Argument
Description
show
Display all battery information for this UPS
test
Execute the battery test immediately.
cal
start | stop
Start or stop Runtime calibration.
Example 1:
To execute battery selftest.
CyberPower >
upsbatt test
Example 2:
To start battery runtime calibration
CyberPower >
upsbatt cal start
date
Description: Show and configure timezone, date format, date, time.
Option
Argument
Description
show
Display system date information for RMCARD
timezone
<time zone offset>
Choose the RMCARD time zone in GMT (Greenwich
Mean Time).
format
mm/dd/yyyy | yyyy/mm/dd |
dd.mm.yyyy | mmm-dd-yy |
dd-mmm-yy | yyyy-mm-dd
Set system date format
yyyy
<number of year>
Set year of system date by AD.
mm
<number of month>
Set month of system date.
dd
<number of date>
Set day of month.
time
<00:00:00>
Set system time.
Example 1:
To define timezone offset as +08:00
CyberPower >
date ti0800
Example 2:
To define the date as March 21, 2015
CyberPower >
date yyyy 2015 mm 3 dd 21