CyberPower Remote Management System
13
Wiring Fault Detecting
If this option is enabled, the UPS will detect if the input wiring is not
grounded or is reversed. It is recommended to insure the UPS wiring has a
ground connection first.
Over Discharge
Protection
When the UPS is in Battery Mode with 0% for the time configured, the
RMCARD will switch the UPS to Sleep Mode and the output will be turned
off.
Enter Sleep Mode After
All Clients Shutdown
If this option is enabled, the UPS will enter sleep mode after utility power
fails and remaining MSDT+2 minutes. For more information about MSDT
please reference the help page in UPS -> PowerPanel List.
Non-Critical Outlet Bank
Turn Off Threshold
When supplying battery power, the UPS will power off this NCL outlet bank
if the remaining battery capacity is lower than this threshold.
Turn off Delay
When supplying battery power, the UPS will power off this NCL outlet bank
after this delay time is met.
Turn On Delay
When utility power is restored, the UPS will restore the output of this NCL
outlet bank after the delay time is met. This prevents excessive power
consumption caused by all the connected equipment starting at the same
time.
[UPS->Master Switch]
Switch the output power of the UPS to be on or off.
Item
Definition
Reboot UPS
Turns the UPS off and back on
Turn UPS Off
Turns the UPS off.
UPS Sleep
This command is available in Utility Power Failure Mode. It puts the UPS in
sleep mode until power is restored.
Note:
Some UPS models may not support this command.
Reset
Resets the pending action to turn the UPS off.
Turn UPS On
Turns the UPS on.
Shutdown/Sleep Delay
Amount of time the UPS waits before it turns off in response to a "Reboot
UPS", "Turn UPS off" or "UPS Sleep" command.
Reboot Duration
After the UPS is turned off, Reboot Duration defines how long the UPS
waits before it turns back on response to "Reboot UPS" command.
Signal PowerPanel
®
Clients to Shutdown
Select this option to warn PowerPanel
®
Business Edition Clients before
turning the UPS off. The Shutdown Delay (MST, Max Clients Shutdown