CyberPower Remote Management System
14
[UPS->Bank Control]
Display the current state of each outlet Bank, and it provides on/off control for the
Non-Critical Outlet Bank. Outlet Number and Device Name displays the device name associated with
the specific outlet.
Item
Definition
Bank Control Options
ON
Turns non-critical bank on immediately.
OFF
Turns non-critical bank off immediately.
Device Name Identification
Outlet #
UPS outlet number as designated by the outlet configuration (varies by
UPS model).
Device Name
Device Name assigned to this outlet.
[UPS->Diagnostics]
The
UPS/Diagnostics
page provides the ability to verify UPS batteries are in
adequate working conditions. You can also complete a runtime calibration to insure an accurate
estimation for the connected load.
Item
Definition
Battery Test
The
Battery Test
will force the UPS to switch to battery power for 10
seconds. This allows the user to verify the battery conditions and
provides information about the battery, including the results and date of
the last battery test. Click the
“
Start
”
button to begin a battery test. The
information will be reported after a battery test completes.
Note:
“N/A” means the UPS model does not have this function.
Last Test Result
The results of the most recent battery test.
Passed
: The battery performed normally during the test.
Failed
: The battery test did not pass.
Follow the steps below if the battery test fails:
Repeat the battery test and replace the batteries if the test fails again.
Contact
CyberPower
for assistance if the battery test fails after the
batteries have been replaced.
Last Test Date
The date of the most recent battery test.
Runtime Calibration
The
Runtime Calibration
ensures the runtime estimate is accurate
with the load and the current battery capacity. When a runtime
calibration is initiated, the UPS will run on battery power until the
batteries are completely discharged. The UPS will then automatically
switch to input power. The batteries will start to recharge upon the
completion of the calibration. Cl
ick the “
Start
”
button to initiate a runtime
calibration. Click the
“
Abort
”
button to stop the runtime calibration. The
information will be reported after a calibration is finished or canceled.