![CyberPower RMCARD205 Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/cyberpower/rmcard205/rmcard205_user-manual_2702133034.webp)
CyberPower Remote Management System
32
Command Descriptions
ups
Description: Show the information about UPS, input, output. And use master switch to control UPS.
Option
Argument
Description
info
show
Display UPS information
input
show
Display UPS input information
output
show
Display UPS output information
Example 1:
To view UPS information
CyberPower >
ups info show
UPS information
Model: OL1000XL
Voltage Rating: 100V
Working Frequency: 40~70 Hz
Power Rating: 1000 VA
Current Rating: 10 Amp
Load Power: 900 Watts
Battery Voltage Rating: 36 V
USB Version: 0.1B
Next Battery Replacement Date: 10/08/2018
NCL Bank: 1
Extended Battery Pack: 4
upsctrl
Description: Enable to use UPS Master Switch.
Option
Argument
Description
reboot
off delay / reboot duration
(eg. 10/10)
off delay:
0 | 10 | 20 | 30 | 60 | 120 | 180 | 300 | 600
reboot duration:
10 | 20 | 30 | 60 | 120 | 180 | 300 | 600
Turns the UPS off and back on. There is
one string include off delay (in seconds)
and reboot duration (in seconds) ,
ex: 10/10 means off delay in 10 seconds
and reboot duration in 10 seconds.
on
Turns the UPS on.
off
0 | 10 | 20 | 30 | 60 | 120 | 180 | 300 | 600
Turns the UPS off. Argument means Turn
Off Delay in seconds.
sleep
0 | 10 | 20 | 30 | 60 | 120 | 180 | 300 | 600
This command is available in Utility Power
Failure Mode. It can make UPS in sleep
mode until power restore. The argument
means Sleep Delay in seconds.