22
CWSI PRODUCT LOAD
SPECIFICATIONS
PRODUCT LOAD SPECIFICATIONS
CP-3000A/DA CONTROL PANEL
Standby AC power
175 ma.
Alarm AC power
190 ma.
Standby DC power
91 ma.
Alarm DC power
200 ma.
WRA-3 REMOTE ANNUNCIATOR
Standby AC power
57ma.
Alarm AC power
57 ma.
Standby DC power
77 ma.
Alarm DC power
175ma.
AR-3A REPEATER
Standby AC power
120 ma.
Alarm AC power
125 ma.
Standby DC power
26 ma.
Alarm DC power
48 ma
RB-10 to 40 relay box
Standby AC power
use AR-3A values as change is negligible
Alarm AC power
add 10 ma. to AR-3A values per relay board
Standby DC power
add 2 ma. to AR-3A values per relay board
Alarm DC power
add 110 ma. to AR-3A values per relay board
PLEASE NOTE: If NACs are not used there is no external load on the panel or repeaters.
The numbers presented above are for control panel and repeater and repeater/relay
combination loads only. Use separate load calculation sheets for NACs loads.