background image

 

23 

 

 
 

A GUIDE TO FIRE PUMPS, CONTROLLERS, AND MONITORING REQUIREMENTS 

NFPA-20 covers Fire Pumps, including fire pump controllers:  

Chapters 10 & 12 cover Electric Motor Driven and Diesel Engine Driven Fire Pump Controllers 
respectively.  Chapter 10 also covers Fire Pump Transfer Switches.  

For required controller alarm contacts see sections:  
10.4.7* Fire Pump Alarm and Signal Devices Remote from Controller.  

10.8.3.12.1  The alternate isolating switch and the alternate circuit breaker (if installed) shall be 
monitored to indicate when one of them is in open or tripped position, as specified in 10.8.3.12(3).  

10.8.3.14 Remote Indication. Auxiliary open or closed contacts mechanically operated by the fire 
pump power transfer switch mechanism shall be provided for remote indication in accordance with 
10.4.8.  

10.4.8 Controller Contacts for Remote Indication. Controllers shall be equipped with contacts (open or 
closed) to operate circuits for the conditions in 10.4.7.2.1 through 10.4.7.2.3 and when a controller is 
equipped with a transfer switch in accordance with 10.4.7.2.4.  

Variable speed controllers have additional contacts to be monitored:  
10.10.8 Indicating Devices on Controller.  
10.10.8.1 Drive Failure.  A visible indicator shall be provided to indicate when the variable speed drive 
has failed.  
10.10.8.2 Bypass Mode.   A visible indicator shall be provided to indicate when the controller is in 
bypass mode.  
10.10.8.3 Variable Speed Pressure Limiting Control Overpressure.  Visible indication shall be 
provided on all controllers equipped with variable speed pressure  limiting control to actuate at 115 
percent of set pressure.  
10.10.9 Controller Contacts for Remote Indication.  Controllers shall be equipped with contacts (open 
or closed) to operate circuits for the conditions in 10.10.8.  

Diesel Fire Pump Controllers:  
12.4.1.3  Separate visible indicators and a common audible fire pump alarm capable of being heard 
while the engine is running and operable in all positions of the main switch except the off position shall 
be provided to immediately indicate the following conditions:  
(1)  Critically low oil pressure in the lubrication system. The controller shall provide means for testing 
the position of the pressure switch contacts without causing fire pump alarms.  
(2)  High engine jacket coolant temperature.  
(3)  Failure of engine to start automatically.  
(4)  Shutdown from over-speed.  

12.4.3 Controller Contacts for Remote Indication. Controllers shall be equipped with open or closed 
contacts to operate circuits for the conditions covered in 12.4.2. These are the minimum required 
alarm contacts.  Numerous others may be supplied as options to the controllers.  

  

 Authored by and thanks to:  James S. Nasby, President ,Columbia Engineering  

   

 847-677-3468  --  FAX 847-677-831

www.columbia-engineering.net

  

 
 

Содержание CP-3000A

Страница 1: ...d service guide by factory certified CWSI trained personnel only and is subject to change at any time as new products are introduced Consult all CWSI UL listed product manuals for proper programming a...

Страница 2: ...ommended Transmitter Outdoor Install 7 FAQs 8 9 Yagi Antenna notes 10 11 OM 3 Antenna notes 12 Zone programming 13 Test Procedure 14 15 FAST Guide Survey procedures 16 18 Keltron Dialer Guide 19 21 Pa...

Страница 3: ...g antenna is on the left The Slave sending antenna is on the right Wiping the base code All Repeaters and devices can have their base code wiped For Repeaters while powered up hold down the SURVEY BUT...

Страница 4: ...Fail means your links are without a doubt not good Please redo your survey procedure for the repeater in question with the FAST tool or survey beep method NOTE You do NOT need to place your installed...

Страница 5: ...up to a minute to link to the system you will then hear a double beep You will know it is correct when you have the LED pattern described above under Normal operation Then do a signal survey at each r...

Страница 6: ...Restarting the panel may cause the AR 3A network to re form differently than the way you powered it up This may not be the optimal signal path and may cause sporadic test failures In addition after wi...

Страница 7: ...power limited wiring must be separated by at least 25 inches within the enclosure HIGH RISE APPLICATIONS Do not stack repeaters directly above each other in stairwells Repeaters should be staggered b...

Страница 8: ...nstall transmitters in a NEMA 3X or NEMA 4 plastic or fiberglass enclosure 12 x 12 x 4 or larger Leave room for vertical and horizontal separation Failure to install the transmitters with proper separ...

Страница 9: ...to your repeater s relay rules setup and make sure your zones are shared as needed between devices repeaters 3 I have an Unknown Device trouble Did you delete a device without removing its battery fir...

Страница 10: ...d near noisy ballasts Is the equipment mounted in electrically quiet areas Is there anything in the way or the walls that could possibly block or significantly hamper the RF signal When you download a...

Страница 11: ...10 Proper Yagi Antenna installation Cable available in 30 and 70 lengths Note Antenna orientation Yagi on Master Receiving Yagi on Slave Transmitting...

Страница 12: ...o come out the front end of the antenna e g where you point the antenna is where 90 of the RF signal is transmitted Typical distance for properly aligned vertical Yagi to Yagi antennas is from 3000 to...

Страница 13: ...sy locations or material that can hinder RF such as metal siding Tips on smaller sites such as historical homes banks churches etc Place on the Control Panel Place on the slave of the Repeater Tips on...

Страница 14: ...ally Third Zone The Tandem feature allows 301s to be programmed to activate each other based on zone programming When two or more 301s share the same number in their zone programming i e zone 100 with...

Страница 15: ...splayed If notification appliance s have been programmed and are activated they will remain activated until the Signal Silence button is pressed At this time the Control Panel can be reset by pressing...

Страница 16: ...displayed To acknowledge the event press the Supervisory Ack button This will silence the internal horn but the condition s will remain displayed Pressing the Reset button will put the CP 3000A back...

Страница 17: ...o digits of the repeater ID on the signal survey screen Place the repeater where the CP 3000A DA would be installed and take the fast to the first probable repeater location Press Signal Silence to pe...

Страница 18: ...form a functional walk test on an installed network you will first need to enroll the FAST to the CP 3000A DA This will create a Checksum Bad trouble on the panel and on any WRA 3 Annunciators install...

Страница 19: ...llowing partially load the battery in the battery socket Placing the magnet next to the vertical post from the chamber cover to the base above the test switch hole push the battery in If you have the...

Страница 20: ...4 respectively 4 10K EOL Resistors 3 on Alarm Zones A B C 1 on Trouble Contact 1 Connection from CP 3000A Trouble Input to Keltron Trouble Output The Dialer Power Supply should be set to 24 Volts cha...

Страница 21: ...20...

Страница 22: ...rt number in the Keltron Software and in your PC s device manager verify change to the matching Port Number For example if the Keltron is using COM port 14 make sure your PC is communicating through p...

Страница 23: ...125 ma Standby DC power 26 ma Alarm DC power 48 ma RB 10 to 40 relay box Standby AC power use AR 3A values as change is negligible Alarm AC power add 10 ma to AR 3A values per relay board Standby DC...

Страница 24: ...ed 10 10 8 2 Bypass Mode A visible indicator shall be provided to indicate when the controller is in bypass mode 10 10 8 3 Variable Speed Pressure Limiting Control Overpressure Visible indication shal...

Страница 25: ...9 3 6 Audible fire alarm signals shall meet the performance requirements of 18 4 3 and 18 4 5 29 3 7 When visible appliances are provided they shall meet the requirements of Section 18 5 Since hearing...

Страница 26: ...en ambient conditions prohibit installation of automatic smoke detection automatic heat detection shall be permitted NFPA 72 2007 4 4 5 Protection of Fire Alarm System In areas that are not continuous...

Страница 27: ...ll create a checksum bad trouble Test Failure On power up if the unit is not able to connect to a Network it will display a Test Failure trouble To clear this trouble press and hold ACK Step Signal Si...

Страница 28: ...SIte Device 8 Once the file has been created import it by clicking on Import File a preview window will pop up click on Proceed and then click on Done 9 If the CP 3000DA panel you are monitoring has a...

Страница 29: ...as indicated in the diagrams Figure 1 and Figure 2 at the end of the document depending upon whether you do or do not have an External Dialer 19 If your COM Port is not COM1 change the COM port on the...

Страница 30: ...tails on how to configure remote monitoring Activity Reports 1 To be able to print out reports you must first download and install ActivityReports msi 2 Once it is installed Double Click on Activity R...

Страница 31: ...s and system messages etc with this software Imports background images configures the COM port etc System Monitor CGSysMon exe This software attaches the COM port on the PC to the serial port on the C...

Страница 32: ...ler data stream the Dialer Interface must be enabled on the CP 3000DA panel Log into the CP 3000DA panel Press Program scroll down to CP 3000DA Setup and press Enter Scroll down to Dialer Setup and pr...

Страница 33: ...aler Trouble Input Figure 2 Hardware Setup With External Keltron Dialer Connection Diagram for CWSite when using an External Dialer CWSI P N MOD DE9MF 2WIRE DE9M DE9F Jumper Box Included in CWSite Cab...

Страница 34: ...test the communications in Demo mode prior to receiving the license file and test some devices 14 Configure your com port on the CWSite PC that will be used on the job site Multiple Jobs Detail Notes...

Страница 35: ...tware on the job site pc if it is different than COM1 Use the Configuration Manager tool to change the COM port Enable the Dialer Serial Data Stream on the CP 3000DA Panel Start the System Monitor pro...

Отзывы: