![CWSI CP-3000A Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/cwsi/cp-3000a/cp-3000a_quick-start-manual_2701250035.webp)
34
Once you have configured the job simply copy the contents of the job sub-folder onto a USB
thumb drive and then copy them onto the destination computer at the job site into its
C:\CWSite folder. The only tweak you may have to do is to configure which COM port you
are using inside the CWSite software on the job site pc if it is different than COM1.
Use the
Configuration Manager
tool to change the COM port.Enable the Dialer Serial Data
Stream on the CP-3000DA Panel.
Start the
System Monitor
program on that PC as described above verifying that it has
connected to your specified COM port.
Start the
System Watch
program and you should be up and running.
Test your devices by creating troubles and alarms as necessary. Test that all devices are
mapped correctly and show up in the CWSIte system.
Содержание CP-3000A