![CWSI CP-3000A Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/cwsi/cp-3000a/cp-3000a_quick-start-manual_2701250016.webp)
15
Proper Testing and Restoral Sequences:
1) Activate desired device(s). Multiple devices may be activated one at a time. Wait
10 seconds in between activation of additional devices.
2)
If notification appliances or tandem smoke detectors have been activated they
can be silenced however
, do not send reset commands out at the same time
alarms are being initiated. Wait for ALL alarm conditions to be displayed
and alarm activation to cease before sending silence commands out.
3)
Once all conditions have been silenced you can either continue testing with the
alarms acknowledged, or, reset the control panel to begin anew.
Supervisory Conditions:
Supervisory devices such as tamper switches, PIV’s, and residential smoke detectors
can be programmed into the CP-3000A. When a
“Supervisory Signal”
is received, the
“Supervisory LED"
will illuminate and the corresponding device(s) will be displayed.
To acknowledge the event, press the
“Supervisory Ack”
button. This will silence the
internal horn but the condition(s) will remain displayed. Pressing the
“Reset”
button will
put the CP-3000A back to System Normal condition.
Typically supervisory signals will not activate appliance circuits however smoke
detectors if required can be enrolled as a supervisory device and activate other tandem
smoke detectors. If a supervisory device is programmed to perform tasks, follow the
sequence above for testing.
Trouble Conditions:
All initiating devices are supervised for trouble conditions to the requirements of UL864
and NFPA 72. Trouble conditions include tamper of a device, low battery, EOL violation,
ac power loss, low battery, etc. When a
“Trouble Signal”
is received the
“Trouble
LED”
will illuminate and the corresponding device(s) and conditions will be displayed.
To acknowledge the event, press the
“Trouble Ack”
button. This will silence the
internal horn but the condition(s) will remain displayed. Press the
“Reset”
button to put
the CP-3000A back to system Normal condition.