OVERDOSING ALARM setting
On the display will appear OVER and time counter
(h:min) will flash. Press + and - to adjust the time,
over which the pump will go in alarm.
Press OK to confirm and to save data.
This will end the alarm setting.
Press ESC to return in measure mode.
RESET procedure
The pump is equipped with a RESET procedure. It can be used any time the user has to reset calibration parameters.
Turn off and turn on the pump
Press once the OK button , it will appear SETPOINT
menu
Press at the same time button + and button - (user
has 15 seconds to make this operation after pressed
OK button)
On the display will appear RESET
ATTENTION: RESET procedure must be performed within 15 seconds from the pump startup. Over this time to
use this procedure, user has to turn off and turn on the pump.
STAND-BY Procedure
When the pump is in functioning, press at the same time - e +, pump stop, in order to exit to this mode press - and + button.
PROGRAMMING (MV RX)
Through the front panel it is possible to set and to modify all the working parameters of operating setting of the pump.
Pump Setup
The pump goes in measure mode, on display
will show the measure's value.
Press OK button to enter in menus; the first is SETPOINT menu, using + and - buttons you will scroll all 3 menus.
ENGLISH
81
Содержание BOMBAPRO PH-RX
Страница 2: ......
Страница 7: ...Limpieza y mantenimiento del electrodo 30 DIBUJOS 117 Bomba 117 Cuerpo bomba 118 ESPAÑOL 7 ...
Страница 32: ......
Страница 35: ...DISEGNI 117 Pompa 117 Corpo Pompa 118 ITALIANO 35 ...
Страница 60: ......
Страница 63: ...DRAWINGS 117 Pump 117 Pump head 118 ENGLISH 63 ...
Страница 88: ......
Страница 91: ...DESSINS 117 Pompe 117 Corps de pompe 118 FRANÇAIS 91 ...
Страница 116: ......
Страница 119: ......
Страница 120: ...CDMU 00203ML1A 03 2016 ...