Operation

Start-Up

Before applying power, make a final check of all wiring 

for continuity, shorts, grounds, etc. It is usually best 

to disconnect external alarms and other equipment 

from the sensor until the initial start-up procedures 

are completed.

After power-up, allow at least 1 hour for the system to 

stabilize before testing the sensors. Because sensors 

are normally located at a distance from the main unit, 

the test time required and accuracy of the response 

checks will be improved if two people perform the 

start-up procedures and use radio contact.

Start-Up test:

1) One person exposes each sensor to hydrogen 

sulfide calibration gas.

2) The second person stays at the control unit to 

determine that each sensor, when exposed to the 

gas, is connected to the proper input and responds, 

causing appropriate alarm functions.

Calibration

The GG-H2S Sensor comes factory calibrated and 

should require only minimal adjustments after 

installation. There are two pots on the preamp that 

are used for calibration.

Note: Never measure sensor output in mA . Always 

use mVDC or VDC voltmeter settings .

Zero Calibration:

 After the unit is installed and has 

been powered up for a minimum of 12 hours, the unit 

can be zero calibrated by the following:

•  Be sure the unit is in clean air or use Zero air 

calibration gas to zero-calibrate the sensor.

• 

Adjust the zero pot until the sensor outputs 40 mV 

from Test [-] to Test [+] (see 

Figure 2

).

Span Calibration:

 The unit is factory calibrated and 

normally does not need to be spanned upon initial 

installation. DO NOT ADJUST THE SPAN POT WITHOUT 

CERTIFIED CALIBRATION GAS! If span adjustment is 

required, the following procedure will span the unit:

• 

Perform zero adjustment before spanning.

• 

Apply span gas at 0.8 L/min.

•  Sensor should react to gas within 10 seconds
•  Once the output signal has peaked (or two minutes 

maximum) adjust the span pot until the correct 

output is achieved (see 

Figure 2

).

Note: Below are a few response characteristics which 

may be an indication that the gas sensor is at or near 

the end of its useful life. If any of these are observed, 

the cell should be replaced:
• 

Slow response to / recovery from calibration gas.

•  Failure of the output to reach 50% of the calibration 

gas value prior to span adjustment.

• 

Unable to achieve correct output during span 

adjustment. 

Содержание GG-H2S

Страница 1: ...Installation and Operation Manual GG H2S HYDROGEN SULFIDE GAS SENSOR...

Страница 2: ...ly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Страница 3: ...es 920 N Tradewinds Pkwy Columbia MO 65201 866 394 5861 sales ctiengineering com www ctiengineering com General description 4 Installation 4 Locating the sensor 4 Installation guidelines 5 Wiring 6 Op...

Страница 4: ...oisture variations that occur during daily process cycles The transmitter circuit board is sealed in potting compound protecting sensitive electronic components and copper tracing from corrosion The s...

Страница 5: ...om mercury vapor lights variable speed drives and radio repeaters Protect sensor from physical damage forklifts etc If mounting on a wall with studs the mounting screws should be screwed into the stud...

Страница 6: ...scale range Wiring Guidelines Always use 3 conductor insulate stranded shielded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot...

Страница 7: ...in mA Always use mVDC or VDC voltmeter settings Zero Calibration After the unit is installed and has been powered up for a minimum of 12 hours the unit can be zero calibrated by the following Be sure...

Страница 8: ...ed Fault red LED On steady if supply voltage is less than 10VDC Status amber LED Blinks once per second if RFI is detected Power green LED On steady to Indicate Power Blinks once per second for 60 sec...

Страница 9: ...installed in the same room All tests and calibrations must be logged Always disconnect power at the controller before performing any wiring at the sensor Sensor Life These electrochemical cells are ex...

Страница 10: ...Linearity 0 5 of full scale Repeatability 1 of full scale Temperature Range 0 F to 120 F 18 C to 49 C Humidity Range 5 to 100 condensing Dimensions 7 7 high x 6 7 wide x 3 8 deep Weight 3 lbs Wiring C...

Страница 11: ...f the product by and person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a proper...

Страница 12: ...ctiengineering com 866 394 5861 GG H2S DOC1 0 20190605...

Отзывы: