GG-H2S

Wiring

Electrical wiring must comply with all applicable codes.

Electrical Power:

 24 VDC regulated, 350 mA.

Output:

 Linear 4/20 mA output. Monitoring 

equipment may have a maximum input impedance of 

700 ohms.

Cable Recommendation:

 20/3 shielded cable 

(General Cable C2525A or equivalent). Length of cable 

to sensor should be no greater than 1,500 feet. 

Monitoring:

 Monitoring equipment must be 

configured to indicate a fault if the signal is below 1 

mA. All signals over 20 mA must be considered high 

gas concentrations. Alarm setpoints should not be 

lower than 10% of full-scale range.

Wiring Guidelines:

•  Always use 3-conductor, insulate, stranded, 

shielded copper cable.

•  Do not pull sensor wiring with AC power cables. 

This can cause electrical interference.

•  If cable runs cannot be made without a splice, all 

splice connections should be soldered.

•  Ground the shield at the main control panel. 

Connect the shield wire in the sensor terminal 

block labeled 

SHLD

.

•  Always disconnect power at the controller before 

performing any wiring at the sensor.

•  To maintain NEMA/IP rating of the enclosure, 

conduit fittings of the same rating or better must 

be used.

Terminal Block Plug (Field Wiring):

SHLD: To case (earth) ground of monitoring equipment

GND: To ground terminal of power supply

+24V: To +24V terminal of power supply

SIG: To signal input of monitoring equipment

Содержание GG-H2S

Страница 1: ...Installation and Operation Manual GG H2S HYDROGEN SULFIDE GAS SENSOR...

Страница 2: ...ly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Страница 3: ...es 920 N Tradewinds Pkwy Columbia MO 65201 866 394 5861 sales ctiengineering com www ctiengineering com General description 4 Installation 4 Locating the sensor 4 Installation guidelines 5 Wiring 6 Op...

Страница 4: ...oisture variations that occur during daily process cycles The transmitter circuit board is sealed in potting compound protecting sensitive electronic components and copper tracing from corrosion The s...

Страница 5: ...om mercury vapor lights variable speed drives and radio repeaters Protect sensor from physical damage forklifts etc If mounting on a wall with studs the mounting screws should be screwed into the stud...

Страница 6: ...scale range Wiring Guidelines Always use 3 conductor insulate stranded shielded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot...

Страница 7: ...in mA Always use mVDC or VDC voltmeter settings Zero Calibration After the unit is installed and has been powered up for a minimum of 12 hours the unit can be zero calibrated by the following Be sure...

Страница 8: ...ed Fault red LED On steady if supply voltage is less than 10VDC Status amber LED Blinks once per second if RFI is detected Power green LED On steady to Indicate Power Blinks once per second for 60 sec...

Страница 9: ...installed in the same room All tests and calibrations must be logged Always disconnect power at the controller before performing any wiring at the sensor Sensor Life These electrochemical cells are ex...

Страница 10: ...Linearity 0 5 of full scale Repeatability 1 of full scale Temperature Range 0 F to 120 F 18 C to 49 C Humidity Range 5 to 100 condensing Dimensions 7 7 high x 6 7 wide x 3 8 deep Weight 3 lbs Wiring C...

Страница 11: ...f the product by and person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a proper...

Страница 12: ...ctiengineering com 866 394 5861 GG H2S DOC1 0 20190605...

Отзывы: