background image

4

GG-H2S

General Description

Installation

The GG-H2S sensor is a +24 VDC, three-wire, 4/20 

mA sensor for hydrogen sulfide which utilizes proven 

electrochemical sensor technology for fast and 

accurate detection. The 0 – 50 ppm detection range of 

the GG-H2S provides real-time continuous monitoring 

of hydrogen sulfide concentrations accurately down to 

5 ppm without false alarms. 

The GG-H2S provides an industry standard linear 4/20 

mA output signal compatible with most gas detection 

systems and PLCs. The output signal is not affected 

by drastic temperature and moisture variations that 

occur during daily process cycles. 
The transmitter circuit board is sealed in potting 

compound, protecting sensitive electronic 

components and copper tracing from corrosion. The 

specially vented chemical-resistant polycarbonate 

enclosure protects the sensor from accidental 

damage, weather and direct hose-hits from clean-up 

crews.

Locating the sensor

One of the most important considerations when 

installing GG-H2S sensors is that they must be easily 

accessible for calibration and maintenance. 

Since hydrogen sulfide is heavier than air, it will tend 

to accumulate in low-lying areas. Mount sensor near 

ground level, typically 18” to 24” from the floor. As a 

general rule of thumb, try to mount sensors within 30 

feet of potential leak sources.

Содержание GG-H2S

Страница 1: ...Installation and Operation Manual GG H2S HYDROGEN SULFIDE GAS SENSOR...

Страница 2: ...ly in the manner described in this manual If the equipment is used in a manner not specified by Calibration Technologies the protection provided by the equipment may be impaired This equipment should...

Страница 3: ...es 920 N Tradewinds Pkwy Columbia MO 65201 866 394 5861 sales ctiengineering com www ctiengineering com General description 4 Installation 4 Locating the sensor 4 Installation guidelines 5 Wiring 6 Op...

Страница 4: ...oisture variations that occur during daily process cycles The transmitter circuit board is sealed in potting compound protecting sensitive electronic components and copper tracing from corrosion The s...

Страница 5: ...om mercury vapor lights variable speed drives and radio repeaters Protect sensor from physical damage forklifts etc If mounting on a wall with studs the mounting screws should be screwed into the stud...

Страница 6: ...scale range Wiring Guidelines Always use 3 conductor insulate stranded shielded copper cable Do not pull sensor wiring with AC power cables This can cause electrical interference If cable runs cannot...

Страница 7: ...in mA Always use mVDC or VDC voltmeter settings Zero Calibration After the unit is installed and has been powered up for a minimum of 12 hours the unit can be zero calibrated by the following Be sure...

Страница 8: ...ed Fault red LED On steady if supply voltage is less than 10VDC Status amber LED Blinks once per second if RFI is detected Power green LED On steady to Indicate Power Blinks once per second for 60 sec...

Страница 9: ...installed in the same room All tests and calibrations must be logged Always disconnect power at the controller before performing any wiring at the sensor Sensor Life These electrochemical cells are ex...

Страница 10: ...Linearity 0 5 of full scale Repeatability 1 of full scale Temperature Range 0 F to 120 F 18 C to 49 C Humidity Range 5 to 100 condensing Dimensions 7 7 high x 6 7 wide x 3 8 deep Weight 3 lbs Wiring C...

Страница 11: ...f the product by and person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a proper...

Страница 12: ...ctiengineering com 866 394 5861 GG H2S DOC1 0 20190605...

Отзывы: