Menu: "Installer / Define /Remote Control".
Remote control function "HC1 Heating mode, ext." is assigned
to terminal block "K24".
Menu: "Installer/Define/Heating Circuit/ Heating Circuit 1". The
normal mode of the remote control signal is defined in the
"HC1 Heating mode ext. config" row.
Menu: "Installer/Settings/Heating Circuit/Heating Circuit 1".
Remote control mode "Off" becomes active when terminal
block K24 is closed.
Open terminal block = Heating mode "On" (in this example).
Closed terminal block = Heating mode "Off" (in this example).
7.10.1.1 Setting the remote control
function
1. Define an "Input"
First, an input must be assigned to the function or
functions to be controlled remotely. This is done in the
"Installer/Define/Remote Control" menu.
In the example, terminal block K24 is selected as the
input for the "HC1 Heat Mode, Ext." function.
2. Configure the function
(Normally Open (NO)/Normally Closed (NC))
Define a normal mode for the external control signal; NO
or NC. The setting is made for the current heating circuit
in the "Installer/Define/Heating Circuit” menu.
For example, a two-way switch can be connected to the
defined input.
If the button when used generates a control signal on
the input (circuit closes), the circuit shall be defined
as NO. When the circuit closes and the control signal
is generated, the heating mode selected in the "HC1
Heating mode, ext." row is activated in the settings
menu for the heating circuit.
3. Setting the heating mode
In the example, the remote control function "Heating
mode, ext." is set to the "Off" position in the "Heating
mode, ext." row. This setting is made in the "Installer/
Settings/heating circuit" menu.
In this example, the normal heating mode is active
("On").
When input K24 is closed (the multi-button in the
example generates a control signal), the status of
the Heating Mode (normal mode "On" > mode "Off")
changes.
Heating remains off until you choose to start the heating
(normal mode "On") by opening terminal block K24 (no
signal on the terminal block).
Содержание EcoZenith i555 Pro 1x230V
Страница 2: ......
Страница 3: ...162 505 72 1 2020 09 22 Installation and Maintenance Manual CTC EcoZenith i555 Pro ...
Страница 152: ...152 CTC EcoZenith i555 Pro 18 Wiring diagram relay card 3x400V ...
Страница 153: ...153 CTC EcoZenith i555 Pro ...
Страница 154: ...154 CTC EcoZenith i555 Pro 19 Wiring diagram relay card 1x230V ...
Страница 155: ...155 CTC EcoZenith i555 Pro ...
Страница 156: ...156 CTC EcoZenith i555 Pro 20 Wiring diagram relay card 3x230V ...
Страница 157: ...157 CTC EcoZenith i555 Pro ...
Страница 158: ...158 CTC EcoZenith i555 Pro 21 Wiring diagram for expansion card ...
Страница 167: ...167 CTC EcoZenith i555 Pro ...
Страница 168: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 505 72 1 2020 09 22 ...