CTC EcoZenith i555 Pro
Alarm messages
Description
[E057] Motor protect high curr.
High current into the compressor has been detected. Press reset and check
whether the alarm recurs. If the fault recurs, contact your installer.
[E058] Motor protect low curr.
Low current into the compressor has been detected. Press reset and check
whether the alarm recurs. If the fault recurs, contact your installer.
[E035] High pressure switch
The refrigerant’s high pressure switch has been triggered. Press reset and
check whether the alarm recurs. If the fault recurs, contact your installer.
[E041] Low brine temp
Incoming brine temperatures from bore hole/ground loop are too low. Press
reset and check whether the alarm recurs. If the fault recurs, contact your
installer to check the dimensions of the cold side.
[E040] Low brine flow
Low brine is often caused by air in the collector system, especially
immediately following installation. Collectors which are too long can also be a
cause. Check also that the brine pump is set to the correct speed. Press reset
and check whether the alarm recurs. Also check the brine filter that has been
installed.
If the fault recurs, contact your installer.
[E063] Comm. err. relay board
[E027] Communication error HP
[E056] Comm. error motor
protection
This message is displayed when the display card (A1) cannot communicate
with the relay card (A2).
This message is displayed when the display card (A1) cannot communicate
with the HP control card (A5).
This message is displayed when the HP control card (A5) cannot
communicate with the motor protection (A4).
[E044] Stop, high compr temp
This message appears when the compressor temperature is high.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E045] Stop, low evaporation
This message appears when the evaporation temperature is low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E046] Stop, high evaporation
This message appears when the evaporation temperature is high.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E047] Stop, low suct. gas exp.
valve
This message appears when the suction gas temperature is low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E048] Stop, low evapor.
This message appears when the expansion valve’s evaporation temperature
is low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E049] Stop, high evap. exp. valve
This message appears when the expansion valve’s evaporation temperature is
high.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E050] Stop, low overheat. exp.
valve
This message appears when the expansion valve’s superheat temperature is
low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E013] EVO off
This message appears when there is a fault with the expansion valve control.
Contact your installer.
Содержание EcoZenith i555 Pro 1x230V
Страница 2: ......
Страница 3: ...162 505 72 1 2020 09 22 Installation and Maintenance Manual CTC EcoZenith i555 Pro ...
Страница 152: ...152 CTC EcoZenith i555 Pro 18 Wiring diagram relay card 3x400V ...
Страница 153: ...153 CTC EcoZenith i555 Pro ...
Страница 154: ...154 CTC EcoZenith i555 Pro 19 Wiring diagram relay card 1x230V ...
Страница 155: ...155 CTC EcoZenith i555 Pro ...
Страница 156: ...156 CTC EcoZenith i555 Pro 20 Wiring diagram relay card 3x230V ...
Страница 157: ...157 CTC EcoZenith i555 Pro ...
Страница 158: ...158 CTC EcoZenith i555 Pro 21 Wiring diagram for expansion card ...
Страница 167: ...167 CTC EcoZenith i555 Pro ...
Страница 168: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 505 72 1 2020 09 22 ...