![CTC Union EcoZenith i555 Pro 1x230V Скачать руководство пользователя страница 73](http://html.mh-extra.com/html/ctc-union/ecozenith-i555-pro-1x230v/ecozenith-i555-pro-1x230v_installation-and-maintenance-manual_2693358073.webp)
73
CTC EcoZenith i555 Pro
7.9.9
Settings External Boiler
Ext. boiler diff °C
5 (3...20)
The value by which the temperature is allowed to drop
below the stop temperature before the external boiler
starts again is set here.
Minimum boiler temp. °C
30 (10...80)
The temperature at which the circulation pump will begin
charging is set here.
This menu bar is only displayed if the temperature
sensor in the boiler has been defined (refer to the
"Installer/Define/External Boiler" menu).
Charge pump delay time (min)
0 (0...20)
The stop delay for the charge pump can be set here.
The charge pump continues to circulate water at the set
time after the external boiler has been turned off. Only
applies to boilers with very small water volumes in order
to avoid overtemperature.
Delay stop ext. boiler
0 (0...240)
If an external boiler is no longer needed, shutting it off
can be delayed. This is used to avoid operation times
too short (risk of corrosion). The boiler is kept hot
according to the set time. Can be set up to 4 hours.
Priority
High (Low/High)
The "Low" option means the external boiler is prioritised
lower than the electric heater(s).
The "High" option means the external boiler is prioritised
over the electric heater(s) if both heat sources are
defined in the system.
Delay priority low
120 (30...240)
Delay of the heat source which has been given "Low"
priority. For instance, if the external boiler has the
priority "High", the electric heater(s) then get(s) the
priority "Low" and is/are delayed by the set number of
minutes before being permitted to engage and assist
in operation. NB: Irrespective of the setting, the electric
heater in the upper tank is used for extra DHW increase.
Menu: "Installer/Settings/External boiler".
Содержание EcoZenith i555 Pro 1x230V
Страница 2: ......
Страница 3: ...162 505 72 1 2020 09 22 Installation and Maintenance Manual CTC EcoZenith i555 Pro ...
Страница 152: ...152 CTC EcoZenith i555 Pro 18 Wiring diagram relay card 3x400V ...
Страница 153: ...153 CTC EcoZenith i555 Pro ...
Страница 154: ...154 CTC EcoZenith i555 Pro 19 Wiring diagram relay card 1x230V ...
Страница 155: ...155 CTC EcoZenith i555 Pro ...
Страница 156: ...156 CTC EcoZenith i555 Pro 20 Wiring diagram relay card 3x230V ...
Страница 157: ...157 CTC EcoZenith i555 Pro ...
Страница 158: ...158 CTC EcoZenith i555 Pro 21 Wiring diagram for expansion card ...
Страница 167: ...167 CTC EcoZenith i555 Pro ...
Страница 168: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 505 72 1 2020 09 22 ...