83
CTC EcoLogic M/L
Menu: "Installer/Settings/Buffer Tank".
Activate this function via an external control signal or a weekly
program.
Menu: "Installer/Define/Heat Pump".
A mode for the external control signal ("Normally Open (NO)" or
"Normally Closed (NC)").
Menu: "Installer/Define/Buffer Tank".
A mode for the external control signal ("Normally Open (NO)" or
"Normally Closed (NC)").
DHW circulation
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
The function allows DHW to circulate in the pipes
between the taps and the DHW tank, ensuring that the
DHW is hot when the taps are opened.
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer / Define/DHW Tank" menu:
• configure the normal mode for the external control
signal (Normally Open (NO)/Normally Closed (NC))
in the "DHW circulation ext. config." row.
In the "Installer/Settings/DHW Tank" menu:
• Access function scheduling from the "DHW
circulation schedule" row.
For more information, refer to the "DHW Tank" section in
the "Installer/Settings" chapter.
Heating buffer tank
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
The buffer tank helps to maintain a more even
temperature in the heating circuit.
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer / Define/Buffer Tank" menu:
• configure the normal mode for the external control
signal (Normally Open (NO)/Normally Closed (NC))
in the "Buffer tank ext. config." row.
In the "Installer /Settings/Buffer Tank" menu:
• set "remote control mode" ("Yes") in the
"Ext. Buffer tank" row.
Access function scheduling from the "Buffer tank
schedule" row.
For more information, refer to the "Buffer Tank" section
in the "Installer/Settings" chapter.
Flow/level switch
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
The flow/level switch produces an alarm on the heat
pump.
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer / Define/Heat Pump" menu:
• configure the normal mode for the external control
signal (Normally Open (NO)/Normally Closed (NC))
in the "Flow/level switch" row.
Menu: "Installer/Define/DHW Tank".
Define a mode (Normally Open (NO) or Normally Closed (NC))
for the external control signal.
Menu: "Installer/Settings/DHW Tank".
Setting a "DHW circulation" weekly program.
Содержание EcoLogic L
Страница 2: ......
Страница 3: ...162 505 61 2 2021 02 25 Installation and Maintenance Manual CTC EcoLogic L M ...
Страница 136: ...136 CTC EcoLogic M L 9 Valves ...
Страница 160: ......
Страница 161: ......
Страница 162: ......
Страница 163: ......
Страница 164: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 505 61 2 2021 02 25 ...