CTC EcoLogic M/L
Menu: "Installer/Defi ne/System Type".
Select "System Type" and defi ne additional heat sources.
4.10
Defi ne
4.10.1
Def. System type
System type
2 (1/2/3/4/5/6)
Select "System Type" 1-6. For more information about
the six system types, see the "Pipe Installation" chapter.
Additional heat (E1)
Yes (Yes/No)
Specify whether additional heat (E1) is connected.
The menu bar is displayed if "System Type" 2, 3, 4, or 5
is defi ned.
Note that when E1 is used in systems 2, 3 and 4,
Heating Circuit 2 cannot be installed because mixing
valve Y2 is used to mix additional heat.
Also note that the EcoLogic "System Type" 5 has no
mixing valve for additional heat (E1).
EcoMiniEl (E3)
No (Yes/No)
Specify whether EcoMiniEl is connected.
This menu bar is displayed if "System Type" 2, 3 or 4 is
defi ned.
Additional heat (E2)
No
(No/0...10V/0...3 steps/0..7 steps)
Specify whether additional heat E2 (0–10 V / 0-3 steps /
0-7 steps) is connected.
This menu bar is displayed if "System Type" 2, 3 or 4 is
defi ned.