59
CTC EcoLogic M/L
Noise reduction schedule
This menu starts a weekly program with limited
compressor speed to reduce the noise level.
The "Weekly Program" chapter describes how to set
schedules.
Compressor stop at brine °C
-5 (-7...10)
This menu defines the brine temperature at which the
compressor will be stopped.
Only applies to liquid-to-water heat pumps.
Brine pump
Auto (Auto/10 days/On)
After installation is complete, you can choose to run the
brine pump constantly for 10 days to remove air from
the system. The brine pump then enters "Auto" mode.
"On" means the brine pump runs constantly.
Only applies to liquid-to-water heat pumps.
Tariff HP
No (No/Yes)
"Yes" means the function can be activated via remote
control.
Read more in the "Def. Remote Control" section of the
"Installer / Define” chapter.
Tariff HP schedule
This menu bar is displayed if a weekly program has
been defined for the "HP Tariff" function.
For more information, refer to:
• chapter "Weekly Program" for schedule setting.
• section "Def. Remote Control" of the
"Installer / Define" chapter for defining the remote
control function.
Passive cooling brine pump on
Yes (Yes/No)
Enable "Yes" if the brine pump should be used for
passive cooling.
Only applies to liquid-to-water heat pumps.
Silent mode, schedule
It is possible to start a weekly program, e.g. during the
night, with limited compressor speed and fan speed to
reduce the noise level.
The "Weekly Program" chapter describes how to set
schedules.
Only applies to CTC EcoAir 600M.
Содержание EcoLogic L
Страница 2: ......
Страница 3: ...162 505 61 2 2021 02 25 Installation and Maintenance Manual CTC EcoLogic L M ...
Страница 136: ...136 CTC EcoLogic M L 9 Valves ...
Страница 160: ......
Страница 161: ......
Страница 162: ......
Страница 163: ......
Страница 164: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 505 61 2 2021 02 25 ...