40
CTC EcoLogic S
10.1.2
Programming CTC EcoEl
CTC EcoEl is only programmed for an electric boiler.
• Hold the "D" button until the next menu is displayed
• If room temperature is displayed, press "D" again to display "LOG/
DIAGNOSIS/INST/MANUAL" (see 1.)
• Press plus (+) to select "INST" (checked box)
• Press "D" 3 times until the box "ECOHEAT/ECOAIR/ECOEL/ECOKM"
appears (2.)
• Press "+" until ECOEL is selected with a checked box.
• Press "D" until box "3." is selected.
Electric boiler lower "PERMITTED" and Temp Lower electric boiler
"30 °C" is a basic setting not to outcompete the heat pump but
activate the electric boiler in winter if the outdoor temperature is lower
than the heat pump’s lowest outdoor temperature. Other possible
options:
• 1. "ELECTRIC BOILER LOWER" "BLOCKED"/"TEMP LOWER
ELECTRIC BOILER" "55 °C" The electric boiler is blocked in spring/
summer/winter and the property owner permits the electric boiler to
operate in winter if necessary.
• 2. "MAX POWER ELECTRIC BOILER" "9 kW"+ "ELECTRIC BOILER
LOWER" "BLOCKED". Recommended in cases where 9 kW is enough
for the entire property and the outdoor temperature is rarely or never
below -20 °C
• Note: "MAX POWER ELECTRIC BOILER" is adjustable 0/3/6/9 kW and
"ELECTRIC BOILER LOWER" is 0/6 kW.
Make sure that there is sufficient electrical power for the property and
that the group fuse/main fuse is adapted for the selected electrical
power.