EZT-430i Communications Manual
Operation
CSZ
EZT-430i
REVC
A.17
*C1
The units of measure and range of an input is dependant upon the configuration of the input and/or
the units of temperature selection (Celsius or Fahrenheit) of EZT-430i . The decimal point position for
the input is an implied value based on the decimal point selection for the input. Thus, a register value
of 345 can represent an actual process value of 345, 34.5, 3.45 or 0.345 depending upon the decimal
point configuration of the input.
6.2 F4S/D Supported Profile Step Data Registers
The following table of data registers provides the list of all data registers associated with downloading profiles
to a Watlow F4S/D. Not all of the F4S/D functionality is provided by EZT-430i , so registers that are shown
“grayed out” in the list represent those functions NOT supported by the EZT-430i automatic program
operation.
EZT-430i is compatible with the profile editor of WatView or any other software that follows the proper
sequence for downloading profiles to an F4. When a profile is downloaded to EZT-430i , it will automatically
ignore the non supported functions so a special profile editor is not required. For the proper method of
downloading profiles to an F4 controller, reference the Profile Programming Procedures in section 7,
Communications, of the Watlow F4S/D User Manual.
Register Address
Parameter Description
Data
*D
Range
*E
*F
Type Low
High
Unit
4000
(0x0FA0)
Profile Number
R/W
1
1
-
4001
(0x0FA1)
Profile Step Number
W
1
64
-
4002
(0x0FA2)
Profile Edit Action
W
*E1
*E1
-
4003
(0x0FA3)
Profile Step Type
W
*E2
*E2
-
4004
(0x0FA4)
Autostart Profile Date or Day
4005
(0x0FA5)
Autostart, Date (month)
4006
(0x0FA6)
Autostart, Date (day)
4007
(0x0FA7)
Autostart, Date (year)
4008
(0x0FA8)
Autostart, Day (of week)
4009
(0x0FA9)
Autostart/Ramp/Soak Time (hours)
W
0
99
*F1
4010
(0x0FAA)
Autostart/Ramp/Soak Time (minutes)
W
0
59
*F1
4011
(0x0FAB)
Autostart/Ramp/Soak Time (seconds)
W
0
59
*F1
4012
(0x0FAC)
Wait/Don’t Wait, Ramp/Soak Steps
4013
(0x0FAD)
Wait For Event 1, Ramp/Soak Steps
4014
(0x0FAE)
Wait For Event 2, Ramp/Soak Steps
4015
(0x0FAF)
Wait For Event 3, Ramp/Soak Steps
Register Address
Parameter Description
Data
*D
Range
*E
*F
Type Low
High
Unit
4016
(0x0FB0)
Wait For Event 4, Ramp/Soak Steps
4021
(0x0FB5)
Wait For Analog 1, Ramp/Soak Steps
4022
(0x0FB5)
Wait For Analog 1, Value, Ramp/Soak Steps
4023
(0x0FB6)
Wait For Analog 2, Ramp/Soak Steps
4024
(0x0FB7)
Wait For Analog 2, Value, Ramp/Soak Steps