EZT-430i Communications Manual
EZT-430i
Data
Registers
CSZ
EZT-430i
REVC 5.11
(standard serial interface)
Starting a Program
Is the
program
already
loaded?
NO
YES
Send program to EZT-430i one step
at a time with a minimum 1 second
pause between write commands:
Send program data – 100 thru 113
- 1 second pause -
Send step 1 data – 114 thru 127
- 1 second pause -
Send step 2 data – 128 thru 141
-1 second pause –
…..
…..
Send last step data
Is
EZT-430i
online?
0=0
NO
Set program start
step. 14=(1-64)
YES
Set program to run.
15=0
Done
-1 second pause –
(EZT-430i begins program download)
NO
Write error
during
program
download?
YES
-20 second pause –
(EZT-430i clears program buffer)