![CSZ EZT-430i Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/csz/ezt-430i/ezt-430i_users-reference-manual_2693060028.webp)
EZT-430i Communications Manual
EZT-430i
Data
Registers
CSZ
EZT-430i
REVC 5.7
(standard serial interface)
*B12
Parameter
Value
Deviation
Alarm
Process
Alarm
Range Low
-18000
SP.Lo
Range High
18000
SP.Hi
*C1
The units of measure and range of a loop input is dependant upon the configuration of the input
and/or the units of temperature selection (Celsius or Fahrenheit) of EZT-430i . The decimal point
position for the loop or monitor input is an implied value based on the configuration of the input.
Thus, a register value of 345 can represent an actual process value of 345, 34.5, 3.45 or 0.345
depending upon the decimal point configuration of the loop or monitor input.
5.2 Automatic Program Registers
The automatic program parameters are a separate group of registers that are used to load programs into
EZT-430i . The manner in which the program steps are configured and sent to EZT-430i is specific and must
be followed exactly.
Each program step consists of 14 data registers. The program must be written one step at a time, using a
multiple write command (0x10) to write the data for all 14 registers at once. This allows programs to be
stored as two-dimensional arrays, of which code can be written to simply index through the array step-by-
step, and transmit the program file to EZT-430i .
The first 14 registers of the program contain specific settings related to the program. These include
hold back bands, ramp units, soak units, the program name and the length of the program (number of
steps).
Register
Address
Parameter Description
Data
*D
Range
*E
*F
Type Low
High Unit
100
(0x0064)
Hold Back Band Loop 1
W
*E1
*E1
-
101
(0x0065)
102
(0x0066)
Ramp Units
W
*E2
*E2
-
103
(0x0067)
Soak Units
W
*E3
*E3
-
104
(0x0068)
Hold Back Band Loop 2
W
*E1
*E1
-
105
(0x0069)
106
(0x006A)
Total Number of Steps
W
1
64
-
107
(0x006B)
Program Name (Chars 1 & 2)
W
*E4
*E4
-
108
(0x006C)
Program Name (Chars 3 & 4)
W
*E4
*E4
-
109
(0x006D)
Program Name (Chars 5 & 6)
W
*E4
*E4
-
110
(0x006E)
Program Name (Chars 7 & 8)
W
*E4
*E4
-
111
(0x006F)
Program Name (Chars 9 & 10)
W
*E4
*E4
-
112
(0x0070)
Program Name (Chars 11 & 12)
W
*E4
*E4
-
113
(0x0071)
Program Name (Chars 13 & 14)
W
*E4
*E4
-