SYMPTOM

PROBABLE CAUSE

CORRECTION

1. Softener Fails to 

    Regenerate 

    Automatically

Power supply plugged into 
intermittentent or dead power source

Connect to constant power source

Disconnected meter cable

Reconnect cable

Improper control valve 
programming

Reset program settings

Defective power supply

Replace power supply

Meter is dirty or defective

Clean or replace meter assembly

2. Loss of Capacity

Increased raw water hardness

Increase hardness setting or decrease 
days between regeneration

Brine concentration and or / quantity

Keep brine tank full of salt at all times. 
Clean it yearly. Salt may be bridged. 
Ensure refill water is over it. 

Resin fouling

Call dealer. Find out how to confirm 
it. Clean the resin and prevent future 
fouling. 

Poor distribution, channeling (uneven 
bed surface)

Call dealer. Check backwash flow. 
Regenerate more frequently

Internal valve leak

Call dealer. Replace spacers, seals 
and / or piston

Resin age

Call dealer. Check for resin oxidation 
caused by chlorine.  Mushy resin.

Resin loss

Call dealer. Check for correct bed 
depth. Broken distributor tube. Air or 
gas in bed: well gas eliminator. Loose 
brine line. 

3. Poor Water Quality

Check items listed in #1 and #2

Bypass valve open

Close bypass valve.

Channeling

Check for too slow or high service 
flow. Check for media fouling.

4. High Salt Usage

High salt setting

Lower brine tank refill time

Excessive water in brine tank

See symptom #7

Constant flow through the unit

Indicates plumbing leak (e.g. toilet 
tank)

Regenerating too frequently

Lower hardness setting or increase 
days between regeneration.

5. Loss of Water Pressure

Scaling / fouling of inlet pipe

Clean or replace pipline. Pretreat to 
prevent.

Fouled resin

Clean resin. Pretreat to prevent. 

Improper backwash setting

Backwash more frequently

Troubleshooting

Содержание Duplex SD128

Страница 1: ...SIGNATURE SERIES 1 Signature Series Duplex Softener Manual Installation Operation Manual...

Страница 2: ...SIGNATURE SERIES 2 www csiwater com Online at Register Your Product Softener Specifications Page 3 Softener Installation Page 5 Service Information Page 8 Troubleshooting Page 13 Warranty Page 15...

Страница 3: ...ions SD48 SD48V SD64 SD64V SD96 SD96V SD128 SD128V Grains Capacity Regeneration Lbs Salt Used Per Tank 24 000 12 0 20 000 7 5 15 000 4 5 32 000 15 0 27 000 9 0 20 000 6 0 48 000 24 0 40 000 15 0 30 00...

Страница 4: ...change Over time the sodium ions used for the exchange process become depleted and must be replenished The water softener provides a Regeneration process whereby brine solution enters the mineral tank...

Страница 5: ...s to prevent heat damage to connections and control valve If using PVC or plastic pipe primers and solvent cements specifically recommended for use with potable water are required Note All plumbing li...

Страница 6: ...ry the brine tank can be placed at a higher level than the resin tank but never at a lower level 2 Install one end of 3 8 O D by 1 4 I D brine line tubing included with unit to 3 8 push fitting tee lo...

Страница 7: ...ecommended although any high quality water softener salt such as solar salt will suffice If iron is pres ent in the raw water use of iron inhibiting salt is recommended The salt level will decrease af...

Страница 8: ...SIGNATURE SERIES 8 Service Information Unit 1 Unit 2 Master Shuttle Power Cord Insert Transformer FRONT VIEW BACK VIEW Brine Line Connection Inlet Outlet...

Страница 9: ...treated The hardness setting is used to calculate the number of gallons of water that can be treated between softener unit regenerations o To edit this setting Press the SET CHANGE button o The lowest...

Страница 10: ...onger the menu will automatically be exited Battery Backup To install the battery standard 9 volt alkaline battery the cover of the shuttle valve must be removed Next insert the battery into the batte...

Страница 11: ...s and plug it back in The valve will try to run again listen for the valve motor trying to run and look to see if the indicator wheel is turning only applicable for the softener slave Units 1 and 2 If...

Страница 12: ...ins and is used in conjunction with the hardness setting to calculate total gallons of treated water available between regenerations This option is identified by the letter c in the left digit The max...

Страница 13: ...d surface Call dealer Check backwash flow Regenerate more frequently Internal valve leak Call dealer Replace spacers seals and or piston Resin age Call dealer Check for resin oxidation caused by chlor...

Страница 14: ...n drain line and or flow control button Injector and or screen is plugged Clean or replace injector and screen No water in brine tank Check for restriction in BLFC Ensure safety float is not stuck Che...

Страница 15: ...resulting from abuse including freezing improper or negligent handling shipping by anyone If the unit has not always been operated within the factory calibrated temperature limits and at a water pres...

Страница 16: ...SIGNATURE SERIES 16 CSI WATER TREATMENT SYSTEMS 710 Orange St Ashland OH 44805 l PH 419 281 6829 l FAX 419 281 2375 www csiwater com...

Отзывы: