Crown Royal Stoves RS7200E Скачать руководство пользователя страница 50

6

Lock Panel (LP)

The keypad can be locked to prevent unwanted tampering 
with the control settings. In the User Menu, change the menu 
item LP selection to On. When the menu is exited and set-
tings are stored, the   or  , and 

 keys will be disabled 

from normal use.
To unlock the keypad, press and hold 

 for 5 seconds. 

The display will change to show LP On. Momentarily press  

 or   to change to Off and then momentarily press 

.     

The control will return to normal operation and the keypad 
will be unlocked.

Binary Input (bIn) and Set Back (Sb)

Binary Input is an option to allow the setpoint temperature 
to set back to conserve energy or for other reasons as 
determined by the user. Set Back determines the number of 
degrees the setpoint temperature will be changed.
An external switch or N.O. relay can be connected to the BIN 
and GND terminals of the control. With bIn set to On, when 
the switch is closed, the control will change the setpoint tem-
perature by the number of degrees set in Sb. In Heat mode, 
setpoint temperature will change lower or cooler. In Cool 
mode, setpoint temperature will change higher or warmer. 
During the time that the switch is closed, bIn will appear in 
the lower left corner of the display. If an alarm is connected 
be sure that the alarm delay time is set long enough to allow 
for the temperature change to avoid a “false” alarm.

Alarm (AL)

This control has an alarm relay that will provide an output to 
alert of a malfunction. The alarm relay output must be con-
nected to an external light, audible alarm or other device as 
needed by the user. If AL is set to 0, the alarm relay will not 
provide any alarm output. If AL is set to a value greater than 
0, the alarm relay output provides indication of three error 
conditions: Temperature Out of Range, Power Loss and Sen-
sor Operation Failure. Although AL must be set to a value 
greater than 0 for any alarm output to be provided, the value 
selected is the time delay, in minutes, before a Temperature 
Out of Range alarm is set. The alarm time delay does not 
apply to Power Loss or Sensor Operation Failure.

OPERATION 

Temperature out of range

 – If the temperature is more than 

5° from the setpoint, continuously for the length of time set in 
AL, the alarm relay output will close. The delay should be set 
to allow for conditions that will cause the temperature to vary, 
such as defrost cycle, opening door for stock removal or 
replacement or Set Back changes. When setting the AL time, 
consideration should be given to these events to prevent a 
false alarm.
If the control set back feature is used to change the setpoint, 
the delay period set in AL should consider the time it takes 
for the system to reach the set back temperature to avoid a 
false alarm.

Power Loss

 – If the temperature control experiences an input 

power failure, the control will close the alarm relay before 
total power of the control is lost. The delay time is not used in 
this event, and the alarm relay will close within seconds of a 
power failure. In addition, the load relay contact change state 
per the Sensor Operation Failure (SOF) setting.
When power returns, the alarm contacts will open. The load 
relay will remain in the SOF position the length of time set in 
Anti Short-Cycle Delay (ASd) after power resumption. The 
display will blink the flame or snowflake icon for this time to 
indicate the load is “locked” out. This is to help protect the 
user’s equipment from damage by short cycle switching.

Sensor Operation Failure (SOF)

 – If in operation, the sen-

sor wiring should become open or shorted, the temperature 
control will begin blinking SOF with SH for shorted or SO for 
sensor open. However, the control will wait approximately 
1 minute before closing the alarm output relay - indicating 
sensor operation failure. If during the 1 minute, the sensor 
“resumes” normal operation, the time is reset and the control 
returns to normal display. The load relay will operate as se-
lected in sensor operation failure (SOF).

Multiple Sensors

The 16E09 is normally operated with one sensor. If an aver-
age temperature of an area is required, 4 sensors may be 
used and wired in the method shown below. If 4 sensors are 
used, they must all be of the same model. 

NOTE

: When using multiple sensors, 4 sensors must be 

used. The control will not operate with 2 or 3 sensors.

Using  the  Alarm  Output  and  power 

stealing  in  combination  – 

When  using 

power stealing mode and the alarm output, it is 

important for the installer to review the wiring circuit 

of the installation to insure no device is present that could 
interrupt electrical power to the temperature control.  Such 
a device could be a defrost timer, as one example, that may 
be used in some refrigeration applications.
If  a  device  is  in  the  system  wiring  that  can  periodically 
disrupt  power  to  the  load  and  the  temperature  control, 
the power stealing mode of the control cannot be used. A 
neutral wire must be connected to the control and select 
the non power stealing mode for the control. This keeps 
power to the control during power interruptions to the load 
and avoids a “false” alarm output.

SPECIAL 

NO

TE

Sensor 3

Sensor 4

Sensor 1

Sensor 2

50

Содержание RS7200E

Страница 1: ...MANUAL EPA QUALIFIED RS7200E INSTALLATION OPERATION MAINTENANCE MANUAL MAILING PO BOX 1237 SHIPPING 2716 CRESCENT DR INTERNATIONAL FALLS MN 56649 PH 866 361 7355 FX 218 283 5786 WEB WWW CROWNROYALSTO...

Страница 2: ......

Страница 3: ...7 BRAZED PLATE SETUP INSTALLATION 18 WATER TO AIR SET UP INSTALLATION 19 STOVE COMPONENTS 20 CONTROL PANEL 21 START UP OPERATION 22 OPERATION 23 WEEKLY MAINTENANCE 24 GENERAL MAINTENANCE 25 27 TROUBLE...

Страница 4: ......

Страница 5: ...series furnaces are often used to heat residential home garages shops barns businesses greenhouses swimming pools spas domestic hot water radiant in floor heat and snow melt applications Model RS7200E...

Страница 6: ...6...

Страница 7: ...ng to eliminate unnecessary smoke Never use gasoline lighter fluids chemicals or oils Furnace Sizing The size of a furnace should be large enough to provide sufficient heat without constant reloading...

Страница 8: ...tube com watch v jM2WGgRcnm0 EPA offers tips on how to properly use a moisture meter to test firewood before using in a wood burning stove or fireplace Wet wood can create excessive smoke which is was...

Страница 9: ...softwood or hardwood The pines spruces and firs are common softwoods and the oaks elms birches and maples are hardwoods Softwoods burn rapidly and are more resinous than the hardwoods therefore they w...

Страница 10: ...ading heat exchanger door or secondary combustion door open Do not store fuel or other combustible materials within marked installation clearances Inspect clean flues and chimney regularly CAUTIONS Ho...

Страница 11: ...prove the location relative to the distance from building and combustibles We recommend a minimum of 25 feet from any building Minimum Clearances to Combustibles Sides Front Back Top Chimney Connectio...

Страница 12: ...not be less than 24 inches wide 24 inches long 3 inches thick Obtain the footprint of the model of furnace you have purchased Place your blocks so that the legs will be in the center of them For a pa...

Страница 13: ...piping does not exceed a total of forty 40 ft When installing chimney please refer to manufacturer s recommendations and requirements for adequate clearances Furnaces come standard with the Selkirk br...

Страница 14: ...gravel or dirt At this point a water barrier is required Several methods are possible but the most important factor is if ground water comes in contact with your heating lines it will be the greatest...

Страница 15: ...furnace plenum If there is an air conditioning evaporator coil in the plenum install the water to air coil after the a c coil If the central heating system is a hot water boiler system a water to wat...

Страница 16: ...in the boiler to prevent damage from loss of circulation due to electrical power failure The Crown Royal Stove shall be installed without changing the function of the controls or rewiring the original...

Страница 17: ...m is too large or too small it must be altered to fit the heat exchanger properly After installation of the add on water to air exchanger the air flow must be increased to fuel the furnaces electric f...

Страница 18: ...intain the temperature in the hot water heater If installed on the hot side the hot water heater needs to be turned off and the hot water heater is now a reservoir If using 1 tubing open ball valve1 3...

Страница 19: ...Water Water to Air Exchanger Water to AirExchanger Boiler Drain Ball Valve Fitting WATER TO AIR SETUP INSTALLATION 19...

Страница 20: ...r Thermowell Solenoid To open and close combustion air opening Door Seals and High Temperature Silicone Fiberglass 1 Rope Nylon 5 rod and steel whip used to clean heat exchanger tubes Includes a drill...

Страница 21: ...button Wait 20 seconds to allow the smoke to evacuate from the furnace before opening firebox door For night filling the fan light switch can be in the light position while filling which will turn on...

Страница 22: ...ed The furnace will continue to feed an air supply to the fire until your aqua stat shut off temperature is reached 180F On this initial start up the water jacket will reach what is called the dew poi...

Страница 23: ...r is to be opened it should always be cracked slightly to allow oxygen to enter and burn off any combustion gases that are present before fully opening Failure to do this could result in sudden igniti...

Страница 24: ...eds to be removed before cleaning each exchanger tube Use the provided wire whip and pole and attach it to a drill to clean each heat exchanger Simply slide the wire whip and pole down each heat excha...

Страница 25: ...irebox secondary burn chamber and exchanger tubes Use a fire retardant closed container to empty ashes into Weekly Maintenance Perform weekly maintenance to heat exchanger tubes and secondary burn cha...

Страница 26: ...as act as an insulator causing incomplete gasification With an excessive ash buildup primary combustion air is restricted and the unit s output will be reduced Damages will result to unit if maintenan...

Страница 27: ...E To avoid a chimney fire ensure that daily weekly month and annual maintenance techniques are being followed If a fire is to occur close all doors including firebox and heat exchanger doors shut down...

Страница 28: ...doors is properly closed and the gasket is completely sealed 3 Check that the solenoid damper plate is opening and closing without hang ups 4 Check that the temperature settings and water levels are...

Страница 29: ...ELECTRICAL TROUBLESHOOTING 29...

Страница 30: ...ELECTRICAL DIAGRAM 30...

Страница 31: ...in sheltered area insufficient wind to disperse smoke C Furnace sizing Similar to other heating appliances furnace should be properly sized based on the estimated heat loss of the served structure II...

Страница 32: ...s properly b Combustion blower wheel spins properly c Blower runs at proper speed verify voltage to blower motor 2 Combustion blower tube not restricted by debris creosote ash etc 3 Flame baffle flue...

Страница 33: ...the wood either too high or too low will affect the amount of visible smoke Wood with a low moisture content less than 10 will burn relatively quicker resulting in some of the fuel going up the chimn...

Страница 34: ...it is loaded B Furnace Size The size of a furnace should be large enough to provide sufficient heat without constant reloading If the target burn time is 12 hours an adequately sized furnace will prov...

Страница 35: ...ed to the heat load so that cold starts and overfilling are avoided Chimney height should be in accordance with the state and local codes as well as surroundings including neighbors These areas along...

Страница 36: ...36...

Страница 37: ...ranty on Crown Royal Stoves it is required to use recommended treatment and submit annual samples for testing Failure to maintain treatment at recommended levels and annual water testing will result i...

Страница 38: ...eeks If testing results are unsatisfactory recommendations of additional treatment will be given These recommendations will need to be performed and a retest is required to maintain warranty o Low lev...

Страница 39: ...nually add of the required amount of treatment this will keep levels balanced Follow directions for collecting of water sample and mail to facility for testing annually Purchasing Water Treatment Wate...

Страница 40: ...induce vomiting If vomiting occurs give fluids again GET IMMEDIATE MEDICAL ATTENTION DO NOT GIVE ANYTHING BY MOUTH TO AN UNCONSCIOUS OR CONVULSING PERSON NOTE TO PHYSICIAN Introduction into the body m...

Страница 41: ...fuels or abuse Greentech Manufacturing Inc is not responsible for the cost of plumbing replacement of antifreeze shipping labor or any other cost other than the replacement of the part or furnace Gree...

Страница 42: ...ng Inc to qualify for warranty Greentech Manufacturing Inc always has the right to decide if the stove will be repaired or replaced To validate this warranty registration must be completed within 30 d...

Страница 43: ...welder to give an estimate to repair the stove which we approve and tell you the percentage covered This warranty is prorated so it will be covered by a percentage After you pay the bill you submit a...

Страница 44: ..._______________________________________________________________ __________________________________________________________________________________________ Repair Required _____________________________...

Страница 45: ...plications which range from refrigeration to heating due to the wide temperature range of the control stated above Typical applications include walk in freezers beverage coolers supermarket display ca...

Страница 46: ...REFER TO PAGE 6 STATUS INDICATOR LED LIT WHEN CONTROLLED LOAD IS ENERGIZED ON SEE NOTE TEMPERATURE UP BUTTON TEMPERATURE DOWN BUTTON MENU BUTTON PRESS TO ENTER MENU MODE REFER TO PAGES 4 5 SW1 Refrige...

Страница 47: ...tional connection to customer alarm equipment Binary Input Gold Plated Contacts 24 VAC Block not used TH Thermostat Hot TR Thermostat Return NTC Temperature Sensor PTC Temperature Sensor Fig 3 Line Vo...

Страница 48: ...ow the set point temperature will operate the load terminal CI indicates the setpoint temperature will be the Cut In temperature CO indicates the temperature will be the Cut Out temperature See Operat...

Страница 49: ...et Point SP Cut In Differential 5 Setpoint temperature 40 Temperature Range 40 Setpoint Cut Out 45 SW1 Cool Set Point SP Cut Out Differential 5 Setpoint temperature 40 Temperature Range HEAT To use as...

Страница 50: ...hould be given to these events to prevent a false alarm If the control set back feature is used to change the setpoint the delay period set in AL should consider the time it takes for the system to re...

Страница 51: ...sistance K 140 60 2 49 149 65 2 09 158 70 1 76 167 75 1 48 176 80 1 26 185 85 1 07 194 90 0 92 203 95 0 79 212 100 0 68 221 105 0 59 Temperature F C Resistance K 40 40 613 31 35 640 22 30 668 13 25 69...

Страница 52: ...ine 1 888 725 9797 www white rodgers com www emerson com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co TROUBLESHOOTING Temp...

Страница 53: ......

Отзывы: