7
III Before Installing
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance
with this manual and the requirements of the authority having jurisdiction.
•
In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the latest
edition of
Installation of Oil Burning Equipment
(ANSI/NFPA31).
•
Where required by the authority having jurisdiction, this installation must conform to the latest edition of
Standard for
Controls and Safety Devices for Automatically Fired Boilers
(ANSI/ASME CSD-1).
2) Make sure that a properly sized chimney is available which is in good condition. Consult the authority having
jurisdiction, Part VII of this manual, and
ANSI/NFPA31 for additional information on venting requirements.
3) Make sure that the boiler is correctly sized. Use an industry accepted sizing method such as the
I=B=R
Guide RHH
published by the Air-Conditioning, Heating and Refrigeration Institute (AHRI).
4) In some cases, boilers installed at altitudes above 2000ft may require a different burner configuration from that at sea level.
Consult the local Crown representative for more information.
TABLE 2.2: OPTIONAL TANKLESS
HEATER RATINGS
MODEL
RATING (GPM)
KSB065
2.25
KSB075
2.25
KSB100
2.50
KSB125
2.75
KSB150
3.00
KSB175
3.25
KSB200
3.50
CAUTION
Fuel oil used with this boiler must conform to ASTM D396. The ASTM D396 standard sets a
5% limit on biodiesel concentration, requires that the biodiesel feedstock comply with ASTM
D6751, and also specifies the procedure that must be used to blend the biodiesel feedstock
with the #2 fuel oil. Attempts to use biodiesel blends not meeting all ASTM D396 requirements
may result in unreliable operation or severe property damage.
Tankless heater ratings based on 40F inlet water, 140F outlet water, and 190F
boiler water. Ratings are also based on 5 minute intermittent draws with 10
minutes between draws.