background image

32

20) Verify that the smoke level still does not exceed #1 and that the draft over fire is -0.02 inch w.c.
21)  Turn off the burner and remove pressure gauge. Install and tighten gauge port plug, than restart the burner.
22)  Check for clean cutoff of the burner. Air in the oil line between fuel pump and nozzle will compress, while burner is 

running, and expand, when burner shuts off, causing oil line pressure to drop and nozzle drip after burner stops. Cycle burner 

on and off 5 to 10 times to purge air completely. 
23)  Check thermostat operation by raising or lowering its set point as required, cycling burner on and off.
24)  Verify primary control operation and safety features according to procedure outlined in the instructions furnished with 

the burner.

25) Check pressure limit control operation. Jump thermostat terminals and allow burner to run until boiler pressure exceeds   

cut-in pressure plus the differential. The burner should shut down. 
26) Check low water cut-off operation. With the thermostat still jumped, fire the boiler and crack the boiler drain valve so that 

water is slowly drained from the boiler. Confirm that the burner shuts down before the water level drops below the bottom 

of the sight glass. 

Do not permit the boiler to fire without water visible in the sight glass

. Add water to the boiler and 

confirm that the burner restarts. Remove thermostat jumper and reconnect thermostat upon check completion.
27) After the boiler has operated for approximately 30 minutes, check the boiler and heating system for leaks. Repair any 

leaks found at once. 
28) After the above checks have been completed, leave thermostat(s) at desired setting. Leave all instructions provided with 

the boiler with owner or in boiler room, displayed near boiler. 
29) After new boiler has been installed and put into continuous operation for several days, clean the boiler of oil, grease, 

sludge, and other contaminants that may have been present in existing piping. This will prevent unsteady water line and water 

carry over into supply main. The boiler boil-out should be done as follows:

a)  Turn off the burner.
b)  Drain water from boiler until about one inch of water is visible in gauge glass.
c)  Run a hose or temporary piping from the boiler drain valve to a location where hot water can be safely discharged. 

Drain approximately five gallons of water from the boiler and mix-in an appropriate amount of an approved boil-out 

compound. Remove safety valve and refill the boiler with prepared solution through funnel. Replace safety valve.

d)    Run a hose or temporary piping from the 1-1/2” skimmer tap on the upper rear section to a location where hot water 

can be safely discharged.  

e)  Start the burner. Run boiler for several hours, boiling the water, without generating steam pressure. Open the water 

feed valve sufficiently to allow a slight overflow of water through the skimmer tapping drain line. Continue boiling  

until water coming out is clear. 

f)  Turn off the burner. Drain hot water from boiler through boiler drain valve to a location where hot water can be 

safely discharged.  Refill the boiler to normal water line level. If water in the gauge glass does not look clear, repeat 

above boil-out procedure again until water clears out.

g)  Conduct pH and Alkalinity test of water in the system. The pH reading should be in 7 to 11 range.

NOTICE

When substantial amount of make-up water is used due to lost condensate, or when 

make-up water is hard or corrosive, water treatment is required. Contact qualified water 

treatment company for recommended water treatment compounds and procedure.

 

WARNING

  Attempts to use burners or burner configurations other than those shown in Table 12.0 

could result in reliability problems, property damage or unsafe operation. 

Содержание KSB Series

Страница 1: ...19134 www crownboiler com WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or loss of life For assistance or additional information consult a...

Страница 2: ...2...

Страница 3: ...s from this instruction manual Authorities having jurisdiction should be consulted before installations are made are made In all cases reference should be made to the following Standards In all cases...

Страница 4: ...e responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when the installation is completed This boiler is not suitable for direct inst...

Страница 5: ...nattended during cold weather unless alarms or other safeguards are in place to prevent such damage DO NOT BLOCK AIR FLOW into or around the boiler Insufficient air may cause the boiler to produce car...

Страница 6: ...CSA C22 1 in Canada and any local regulations WARNINGS FOR THE INSTALLER WARNING This boiler must be properly vented The chimney must be inspected for any obstructions and cleaned prior to each heatin...

Страница 7: ...IV Field Assembly 8 V Locating the Boiler 11 VI Air for Combustion Ventilation 12 VII Venting 17 VIII System Piping 19 IX Indirect Tankless Water Heater Piping 21 X Fuel Line Piping 23 XI Wiring 26 X...

Страница 8: ...TIONS GAL HR MBH Sq ft MBH 1 20 1 50 1 75 1 90 KSB175 KSB200 KSB150 B C BURNER INPUT 0 65 0 75 1 00 79 A 85 1 HEATING CAPACITY NET AHRI RATING STEAM AFUE 91 85 1 KSB065 KSB075 KSB100 KSB125 DIMENSIONS...

Страница 9: ...industry accepted sizing method such as the I B R Guide RHH published by the Air Conditioning Heating and Refrigeration Institute AHRI 4 In some cases boilers installed at altitudes above 2000ft may...

Страница 10: ...Pipe Fittings Loose Flue Baffles KSB100 Only b The burner carton consisting of the following items Oil Burner assembly complete with cord and nozzle installed This nozzle is for the highest firing ra...

Страница 11: ...the instruction manual envelope and apply it next to the rating plate TABLE 4 0 FIELD ASSEMBLY COMPONENTS BURNER1 BOILER MODEL KSB0652 KSB075 KSB100 KSB125 KSB150 KSB175 KSB200 BECKETT CROWN CARTON PA...

Страница 12: ...10 FIGURE 4 1 FIELD INSTALLATION OF FLUE BAFFLES...

Страница 13: ...this clearance is reduced A 24 service clearance is required on the left side of boilers equipped with float type low water cut offs This is to facilitate low water cut off maintenance 2 If listed Ty...

Страница 14: ...osphere have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed Weather stripping has been added on openable windows and doors Caulking and sealants ar...

Страница 15: ...of adjoining spaces only if no doors are installed between them If doors are installed between the boiler room and an adjoining space do not consider the volume of the adjoining space even if the door...

Страница 16: ...an opening takes into account the blocking effect of mesh grills and louvers Where screens are used they must be no finer than 4 x 4 mesh For Buildings of Unusually Tight Construction 1 Openings must...

Страница 17: ...15 FIGURE 6 2 ALLAIR FROM OUTDOORS VIA VENTILATED ATTIC FIGURE 6 3 ALLAIR FROM OUTDOORS USING OPENINGS INTO BOILER ROOM...

Страница 18: ...16 FIGURE 6 4 ALLAIR FROM OUTDOORS USING HORIZONTAL DUCTS INTO BOILER ROOM...

Страница 19: ...nry Chimney The masonry chimney must be constructed in accordance with the latest edition of Standard for Chimneys Fireplaces Vents and Solid Fuel Burning Appliances NFPA 211 and lined with a clay lin...

Страница 20: ...e proper clearance from the horizontal vent connector to combustibles and the proper pitch called for in 7 above 9 Vent pipe should be installed above the bottom of the chimney to prevent blockage 10...

Страница 21: ...occur Short cycling on low water Boiler or system Flooding Hammering Failure to heat one or more radiators VIII System Piping WARNING Install boiler so that the electrical components are protected fr...

Страница 22: ...require Hartford loops 5 Do not use a check valve in place of or in addition to a Hartford loop on a gravity return system 6 Pipe the fill connection from a clean source of cold water When the water...

Страница 23: ...for wiring information 2 Y Strainer Install a Y strainer to prevent sediment from accumulating inside the indirect water heater 3 Check Valve Prevents gravity circulation through the indirect water he...

Страница 24: ...ed to excessive temperatures when no water is flowing through the coil 3 DHW Pressure Relief Valve Required Limits the pressure in the tankless heater and piping Use an ASME constructed valve designed...

Страница 25: ...fer also to the instruction manuals provided with the burner WARNING Under no circumstances can copper with sweat style connectors be used Do not use compression fittings Oil piping must be absolutely...

Страница 26: ...ld be converted to a one pipe gravity system as doing so will result in lower inlet line flow and longer filter life d TWO PIPE LIFT SYSTEM used when a fuel oil storage tank is located below an oil bu...

Страница 27: ...uel pump Use heavy wall copper tubing in a continuous run On two pipe systems the return line should terminate 3 4 above suction line depth within the storage tank Refer to the pump manufacturer s ins...

Страница 28: ...he National Electrical Code ANSI NFPA 70 Disconnect electrical power to the boiler and heating system before servicing Positively assure that no voltage is present Lock electrical boxes to prevent som...

Страница 29: ...ring Install the L4006A with the 3 4 NPT well in the 3 4 tapping in the center of the coil plate Make sure that the sensing bulb of this control is fully bottomed out in the well Route the wire harnes...

Страница 30: ...28 FIGURE 11 0 120V BOILER CONNECTIONS DIAGRAM See Figs 11 1a c for burner and low voltage thermostat wiring Beckett 7505 FIGURE 11 1a CONNECTIONS DIAGRAM FOR BECKETT BURNER PRIMARY CONTROL...

Страница 31: ...29 Carlin 40200 FIGURE 11 1b CONNECTIONS DIAGRAM FOR CARLIN BURNER PRIMARY CONTROL Riello 530SE FIGURE 11 1c CONNECTIONS DIAGRAM FOR RIELLO BURNER PRIMARY CONTROL...

Страница 32: ...30 FIGURE 11 2 INDIRECT WATER HEATER FIELD WIRING...

Страница 33: ...s for more details 14 Immediately upon firing the boiler check the smoke level If the smoke level is in excess of a 1 open the air adjustment to bring the smoke level below a 1 15 Make sure that the o...

Страница 34: ...has been installed and put into continuous operation for several days clean the boiler of oil grease sludge and other contaminants that may have been present in existing piping This will prevent unste...

Страница 35: ...DRAFT OVER FIRE in w c MAX SMOKE bacharach scale FLUE CO2 MIN 11 0 11 0 11 0 11 0 11 0 11 0 11 0 MAX 12 5 13 0 13 0 13 0 13 0 12 5 13 0 0 02 0 02 0 02 1 0 02 0 02 1 1 1 1 NONE NONE NONE NONE 1 0 02 0...

Страница 36: ...DEL DEL HAGO DEL NOZZLE 0 60 60A 0 85 60W 1 00 60A 1 25 60B 1 35 45B 1 65 45B PUMP PRESS psi 150 150 150 150 150 150 TURBULATOR 0 2 3 3 1 5 2 AIR SHUTTER SETTING 2 60 2 85 3 8 4 5 3 3 8 DRAFT OVER FI...

Страница 37: ...or other deterioration Replace any defective vent system components a Temporarily install a 1 1 4 inch or larger full port ball valve in place of the 1 1 2 plug Temporarily pipe the outlet of this val...

Страница 38: ...valve immediately if valve fails to relieve pressure 11 Open fuel line shut off valve s and restore electrical power to the boiler 12 Fire the boiler and check it out using the procedure outlined in S...

Страница 39: ...g sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clothes separately f...

Страница 40: ...gas leakage into the building resulting in odor complaints 6 Dirt The use of a fuel filter is required Accidental accumulation of dirt in the fuel system can clog the nozzle or nozzle strainer and pro...

Страница 41: ...70021 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 17 FLAME INSPECTION COVER 290022 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 18 5 16 18 X 3 4 HEX HEAD CAP SCREW 900400 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 19 1 2 x 1 SE...

Страница 42: ...450 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 48 GLASS SET 950078 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 49 PRESSURE LIMIT CONTROL L404F1367 3503800 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 50 90 DEGREE BRASS PIGTAIL...

Страница 43: ...41...

Страница 44: ...42 Manufacturer of Hydronic Heating Products P O Box 14818 3633 I Street Philadelphia PA 19134 www crownboiler com...

Отзывы: