15
LED2 - Double Flash amber
Master Device
No wireless communication to one or more configured slaves - attempting
to re-establish connection
Slave Device
No wireless communication to master - attempting to re-establish
connection
LED2 - Long Single Flash Amber
Master Device
Indication to show a slave has just been unlearnt from the network (see
LED2 - Double Flash red
Master Device
Network fault no wireless communication to one or more configured slave
devices
Slave Device
Network fault no wireless communication to master
LED2 - Triple Flash Green
Master/Slave Device
Learn/Unlearn was successful or force communications was successful
LED2 - Triple Flash Red
Master/Slave Device
Learn/Unlearn was unsuccessful or force communications was
unsuccessful
1.4.3 LED3 - Alarms (Red LED)
Indicates a Detective Net gas alarm or a network alert.
Single flash
Gas alarm event
Double flash
Network alert event
1.4.4 LED4 – Master/Slave (Green LED)
Indicates if the Detective Net is configured as a master or a slave device.
Single Flash green
Device configured as Master Device
LED off
Device configured as Slave Device
1.4.5 Battery Indication LED (Red LED)
Indicates low battery status on Detective Net device.
Single Flash red
Low Battery
1.4.6 LED repetition rates
LED repetition flash rate on start up (i.e. whilst the network is configuring and stabilising) will be once
every 5 seconds.
Once the network is stabilised the flash rate is decreased to once every 30 seconds to conserve
battery life.