Page 4
INPUTS
The PW-8 has 5 separate programmable monitored analogue inputs,
4 x Programmable, multi-state detection inputs
1 x Programmable tamper input ( with optional Key-switch functions)
Each input must be terminated with short circuit or the appropriate value of end-of-line resistors, even if the input
is unused.
ZONE INPUTS
- Each of the 4 zone inputs can be assigned one of the following configuration options
Type 1 4 ZONE Short circuit input No-End-of-Line (EOL).
Type 2 4 ZONE End-of-Line 2k2 (EOL) with no tamper.
Type 3 8 ZONE End-of-Line (EOL) No Tamper.
Type 4 8 ZONE End-of-Line (EOL) With open & short circuit Tamper.
The following table shows end-of-line resistor configurations.
The reference to LEDS in bold below relate to the program option setting at address P130E.
Type 1 Type 3
Type 2
Type 4
Zone
Type
Low Zone
Resistor
Hi Zone
Resistor
Tamper
End-of-line
Type 1 (4 Zone)
LEDS 1-4 off, 5-8 off
N/A (Short circuit)
N/A
N/A
Type 2 (4 Zone)
LEDS 1-4 on, 5-8 off
2k2
-
-
Type 3 (8 Zone)
LEDS 1-4 off, 5-8 on
4k7
8k2
N/A
Type 4 (8 zone)
LEDS 1-4 on, 5-8 on
4k7
8k2
2k2
LED at Addr. P130E
Zone Relationship
LED at Addr. P130E
Zone Relationship
LED #1
Zone 1 Short or EOL
LED #5
Zone 5 Enabled
LED #2
Zone 2 Short or EOL
LED #6
Zone 6 Enabled
LED #3
Zone 3 Short or EOL
LED #7
Zone 7 Enabled
LED #4
Zone 4 Short or EOL
LED #8
Zone 8 Enabled
n/c
n/c
n/o
2k2
Alarm Contact
n/c or n/o
4k7
Alarm Contact
n/c or n/o
8k2
2k2
Tamper
Alarm Contact
n/c or n/o
4k7
Alarm Contact
n/c or n/o
8k2
Tamper