Page 39 

PROGRAMMING TELEPHONE NUMBER REPORT FORMAT 

 
This block of addresses (P241E - P244E) are used to set the reporting format which will be sent when an alarm 
occurs for each of the telephone numbers. 

P241E-Telephone #1 Options  1E

       Contact ID 

(

Default = 2

)                            

2E

       Domestic Dial   

**(see location 181-184 option 7)

 

                                                 

3E

       spare 

                                                 

4E

       Voice Dialer 

                                                 

5E      

spare 

                                                 

6E

       4 + 2 (Pulsed) 10 pps (1400 hz Handshake, 1900 hz transmit Tone) 

                                                 

7E      

4 + 2 (Pulsed) 10 pps (2300 hz Handshake, 1800 hz transmit Tone) 

                                                 

8E      

spare

 

                                                 9E      

spare

 

                                                 10E    

4 + 2 (Pulsed) 20 pps (1400 hz Handshake, 1900 hz transmit Tone) 

                                                 11E    

4 + 2 (Pulsed) 20 pps (2300 hz Handshake, 1800 hz transmit Tone) 

                                                 

12E    

spare

                                                

                                                   13E   

4 + 2 DTMF 

 
 
 
 
 
 
 
 
Option 1       

Contact ID

 - If this option is set for the telephone number, the panel will send a Contact ID message 

                    to a Monitoring Station.  
 
Option 2      

Domestic Dial

 - If this option is set for the telephone number, the panel is expecting to dial a residential 

telephone number when an alarm occurs. The message sent consists of a siren tone over the phone to 
PW-8 the person called that an alarm is in progress. The alarm can be cancelled by the person called by 
pressing any button on a touch tone phone during the quiet period. If the alarm is cancelled by a valid 
user code the dialer will stop any further calls.

 If the alarm is not reset or kissed off, the dialer will 

attempt to report the alarm/s again when the test time comes around. If you don’t wish this to 

happen turn off all of the test days at P404E.  

**(see location 181-184 option 7) 

 
Option 3       pager 
 
Option 4      

Voice Dialer  - 

If the optional voice board is fitted to the panel then selecting this option for the telephone 

number will allow preset voice messages to be sent via the telephone following an alarm. 

If the alarm is 

not reset or kissed off, the dialer will attempt to report the alarm/s  again when the test time 
comes around. If you don’t wish this to happen turn off all of the test days at P404E.  

Option 5       spare

 

 
Option 6      

4 + 2 (10 pps)  - 

This option transmits a 4 digit account code followed by a 2 digit event code to a central 

monitoring  station. The handshake tone from the monitoring station must be 1400 hz and the transmit 
tone from the panel will be at 1900hz at 10 pulses per second.  

 
Option 7      

4 + 2 (10 pps)  - 

This option transmits a 4 digit account code followed by a 2 digit event code to a central 

monitoring station. The handshake tone from the monitoring station must be 2300 hz and the transmit 
tone from the panel will be at 1800hz at 10 pulses per second.  

 
Option 8       spare 
 
Option 9       spare 
 
Option 10    

4 + 2 (20 pps)  - 

This option transmits a 4 digit account code followed by a 2 digit event code to a central 

monitoring station. The handshake tone from the monitoring station must be 1400 hz and the transmit 
tone from the panel will be at 1900hz at 20 pulses per second.  

 
 
Option 11    

4 + 2 (20 pps)  - 

This option transmits a 4 digit account code followed by a 2 digit event code to a central 

Phone 1 Format  
2  

Содержание PowerWave-8

Страница 1: ...anelCommunicator PowerWave 8 P N 7111260 Rev H N A Version 8 72 01 2004 Installationand ProgrammingGuide Page 1 1 2 3 4 A 5 6 7 8 B Ready Byp System Trouble Program 7 4 1 2 3 5 6 9 8 0 ENTER PROGRAM B...

Страница 2: ...24 TWO TRIGGER TIMER 24 DAY MODE TIMER TO KEYPAD BUZZER 24 OUTPUT TIMING OPTIONS 25 LOADING RADIO ZONES 26 RADIO ZONE OPTIONS 26 LOADING RADIO PENDANTS 27 RADIO PENDANT OPTIONS A 28 RADIO PENDANT OPTI...

Страница 3: ...ECIEVER KEYPAD BUS CONNECTION EXT KEYPADS OUTPUT BOARD RX 40 RECIEVER OPTIONAL KEYPAD CONN POWER FOR DETECTORS ACCESSORIES 2K2 ZONE DETECTORS INPUTS OUT 1 1A max 12V OUT 2 1A max 12V OUT 4 100mA max 1...

Страница 4: ...table shows end of line resistor configurations The reference to LEDS in bold below relate to the program option setting at address P130E Type 1 Type 3 Type 2 Type 4 Zone Type Low Zone Resistor Hi Zon...

Страница 5: ...PW 8 to the incoming telephone line from the street The communicator uses this line for reporting LINE OUT This pair of terminals is used to connect telephones and other communication equipment to th...

Страница 6: ...ction must be disconnected before the power is disconnected Similarly when reconnecting the dialer it is necessary to power up the Alert before connecting the dialer to the Telecom Network Connection...

Страница 7: ...splay system menus and prompts trouble indications time date clock viewable event buffer all system parameters programming customizable zone labeling LED KEYPAD LED indicators READY ARMED TROUBLE 4 Ke...

Страница 8: ...ia a 4 or 5 wire data security cable A maximum of 8 LED keypads can be connected each wired in parallel A 5th wire may be used to provide a Listen in facility at the keypad when an PW8 communicator pa...

Страница 9: ...ing DURESS ALARM Duress Alarm TROUBLE AREA A B On Steady Flashing SUPERVISED RADIO ALARM Supervised Radio Passive Infra Red SYSTEM TROUBLE LED s 1 4 On Steady Flashing Flashing ZONE INACTIVITY ALARM Z...

Страница 10: ...default each keypad comes addressed as 1 Switches A B and C at ON position To assign a keypad as address 2 change switch A to OFF position To assign a keypad as address 3 change switch B to OFF posit...

Страница 11: ...mally used at the end of a button sequence The CONTROL button if enabled is used to isolate day zone audible alarms if temporarily not required and or to directly control outputs if programmed ICON LE...

Страница 12: ...Program light will Flash Note Default Installer Code Code 11 is 000000 You are now in Installer Program Mode Any program addresses may be viewed or changed in this mode ACCESS TO CLIENT PROGRAM MODE F...

Страница 13: ...ode you must first be in client or installer program mode then select the address from 1 10 If there is already a code programmed at this address it will be flashed back to you Now enter the code then...

Страница 14: ...31E 1E Invert output Default off P34E on 2E Flash output Default off 3E Single pulse to output Default off 4E Lockout output once reset Default off 5E Siren Driver to output Default off 6E Control but...

Страница 15: ...day zone to output timer P211E P218E P32E P38E As per P31E above for Outputs 2 8 PROGRAMMING OUTPUT OPTIONS cont OUTPUT OPTIONS B P41E P48E In this block of addresses P41E relates to output 1 P42E re...

Страница 16: ...en a Stay Mode zone is in alarm during the STAY state only this block of addresses allows individual zones to be mapped to selected outputs The default setting is that zones 1 8 will turn on output 2...

Страница 17: ...e 5 8 P91E Zone Tamper to Output 1 Options Zone Tampers 1 8 Default 1 8 P92E Zone Tamper to Output 2 Options Zone Tampers 1 8 Default 1 8 P93E Zone Tamper to Output 3 Options Zone Tampers 1 8 Default...

Страница 18: ...code is entered to set Area A Stay Mode If a keypad is assigned to both Partitions this option should be set to allow individual arming of Stay Mode for each area Option 3 CODE required to set If this...

Страница 19: ...t to zero Option 3 Disarm indication to output This option will turn the output on when Area A is Disarmed The output will turn on when the Area A is disarmed and turn off when the Area is Armed or in...

Страница 20: ...e press of the button If the option is off then the alarm can only be unset by a valid code even during the exit delay time Option 5 STAY button can disarm Stay Mode This option allows the Stay button...

Страница 21: ...nt the length of the pulses is set by the pulse timer P221E P228E Option 7 Pulse on Arming to output This option will map a pulse to the Output each time Area B is armed the length of the pulses is se...

Страница 22: ...es which are BYPASSED become re included once the alarm has been set then unset 24 hour zones however remain BYPASSED until manually re included again Ev ery time the alarm is set or unset with zones...

Страница 23: ...mal security zone when armed Day zones can be temporarily disabled with the Control button if programmed to do so P144E Permanent Day Zone CHIME Zones 1 8 Default No zones This option allows programmi...

Страница 24: ...P306E Zone 6 Entry Delay Time 0 9999 Seconds Default 0 Sec P307E Zone 7 Entry Delay Time 0 9999 Seconds Default 0 Sec P308E Zone 8 Entry Delay Time 0 9999 Seconds Default 0 Sec PROGRAMMING EXIT DELAYS...

Страница 25: ...ec P207E Output 7 Delay On Time Default 0 Sec P208E Output 8 Delay On Time Default 0 Sec OUTPUT DAY MODE TIME P211E P218E 0 99 1 10th Second The output d ay mode timer is how long an output will turn...

Страница 26: ...active 6E Freelink with checksum Non supervised 11E spare 12E spare 21E spare 31E spare 32E spare 33E spare Option 1 Crow AE Series Battery Low If a Crow AE radio pendant or PIR is used on the PW 8 ra...

Страница 27: ...initiated and the Led on the RX 40 board will flash The radio pendant you wish to load must transmit a signal within 30 seconds of entering learn mode otherwise the panel will time out and no code wi...

Страница 28: ...endant can Disarm This option assigns the Disarm function to a pendant The partition s it will disarm has to be selected at options 1 2 Option 5 Pendant can turn Stay Mode On This option assigns the S...

Страница 29: ...arm If this option is on pressing the pendant button will produce a pendant panic alarm The Panic alarm can also be silent at the keypad or sound the keypad buzzer see P175E Option 7 Delayed Panic Ala...

Страница 30: ...ll keypads 1 8 KEYPADS FIRE 4 6 OR CHIME B ENABLED By pressing the buttons 4 6 or CHIME B simultaneously it is possible to create a Fire alarm report to the dialer If you want this Fire function enabl...

Страница 31: ...tional panel functions P169E 1E Turn Off keypad LEDS at the end of exit time Default off 2E Keypad Panic Button delayed or instant Default off 3E Installer Code has direct access to Program Mode Defau...

Страница 32: ...only be armed if all zones are sealed Ready LED On with the exception of those zones which can be unsealed if programmed at address P145E Option 5 No audible keypad beep on supervised radio fault If a...

Страница 33: ...tered at addresses P408 P411 then no daylight saving adjustments will apply Otherwise set up the parameters for the country concerned and the adjustments will become automatic every year P408E Dayligh...

Страница 34: ...zones are working properly By pressing the Program or Enter buttons walk test mode can be terminated and normal programming resumed All Walk test activities will go into the event memory for display...

Страница 35: ...249E and let the phone ring until this number is reached at which time the panel will answer the call The second method is to use fax defeat which entails calling the panel and letting it ring no more...

Страница 36: ...panel can report this alarm to a central monitoring company if this option is on Option 6 Report Line Failure If a telephone line failure is detected the panel can report this alarm to a central monit...

Страница 37: ...e disarming of the panel to show it has been turned off by a valid user Option 4 Send Stay Mode unset after activation If this option is on the panel will not normally send a Stay Mode Arm Disarm sign...

Страница 38: ...on at All Times Default off PROGRAMMING TELEPHONE NUMBERS The panel can be programmed with up 4 telephone numbers The numbers can be up 16 digits long Dial modifiers such as Pause can be programmed in...

Страница 39: ...e comes around If you don t wish this to happen turn off all of the test days at P404E see location 181 184 option 7 Option 3 pager Option 4 Voice Dialer If the optional voice board is fitted to the p...

Страница 40: ...the dialer monitors the status of the dialing tone to determine whether the call is valid or not If the call is not valid i e Engaged the panel will know and hang up the call and try again Option 3 Bl...

Страница 41: ...t 130 P322E Zone 2 Contact ID Code 3 Digit Number Default 130 P323E Zone 3 Contact ID Code 3 Digit Number Default 130 P324E Zone 4 Contact ID Code 3 Digit Number Default 130 P325E Zone 5 Contact ID Co...

Страница 42: ...et the 4 2 code that a Zone will transmit when it is restored following an alarm P521E Zone 1 4 2 Code 2 Digit Number Default 11 P522E Zone 2 4 2 Code 2 Digit Number Default 12 P523E Zone 3 4 2 Code 2...

Страница 43: ...the 4 2 code for Miscellaneous restore reporting functions P529E System Tamper Restore 4 2 Code 2 Digit Number Default 87 P534E Panic Alarm Restore 4 2 Code 2 Digit Number Default 91 P535E Fire Alarm...

Страница 44: ...ms the alarm system via there Radio Key P561E Armed by Radio User 1 4 2 Code 2 Digit Number Default 61 P562E Armed by Radio User 2 4 2 Code 2 Digit Number Default 62 P563E Armed by Radio User 3 4 2 Co...

Страница 45: ...Alarm Voice Message Number Default 1 P261E Medical Alarm Voice Message Number Default 1 P262E Battery Low Voice Message Number Default 1 START MESSAGE NUMBER FOR DTMF CONTROL This address P250E sets t...

Страница 46: ...g station PLEASE NOTE If daylight saving adjustments are set P408 P413 do not set the value at P402 to be a value between 1 3 am otherwise unwanted results will occur at the start finish of daylight s...

Страница 47: ...P25E User Options Code 5 Default 1 6 4 Code can Disarm Area Page 14 P26E User Options Code 6 Default 1 6 5 Code can arm Stay Mode Page 14 P27E User Options Code 7 Default 1 6 6 Code can disarm Stay Mo...

Страница 48: ...P67E Stay Mode Zone Alarms 1 8 to Output 7 Default None Page 16 P68E Stay Mode Zone Alarms 1 8 to Output 8 Default None Page 16 Mapping 24 Hour Zone Alarms To Outputs P71E 24 Hour Zone Alarms 1 8 to...

Страница 49: ...ed Before Code to Set Stay Mode 3 Code required to Set 4 Arm Button can disarm during Exit Delay 5 Stay Button can disarm Stay Mode at any time 6 No Exit beeps to Keypads in Stay Mode 7 Enable Key swi...

Страница 50: ...41E Non Latching 24 Hour Zone Zones 1 8 Default No zones Page 23 P142E Lockout Zone Zones 1 8 Default No zones Page 23 P143E Day Zone CHIME Zones 1 8 Default No zones Page 23 P144E Permanent Day Zone...

Страница 51: ...o fault 6 No audible keypad beep on Zone Inactivity Timeout 7 Control Button Disables Day Zones 8 Silent 24 Hour Zone No Keypad Beep Keypad Partition Assignment P171E Keypads Assigned To Partition A V...

Страница 52: ...nd Test Calls 7 Auto Kiss off in Domestic or voice Mode 8 Spare option 7 must set to ON if working in domestic protocol Dialer Programming Options P185E Dialer options P185E Options Default 1 2 7 Page...

Страница 53: ...hout the call in Disarm State only 5 Enabled Throughout the call in Armed State only 6 Enabled Throughout the call in Stay Mode State only 7 Listen in Enabled when the panel answers a call 8 Enabled a...

Страница 54: ...nds Default 20 2 Sec Page 25 P227E Output 7 Pulse Time Value 0 99 1 10 Seconds Default 20 2 Sec Page 25 P228E Output 8 Pulse Time Value 0 99 1 10 Seconds Default 20 2 Sec Page 25 Two Trigger Timer P22...

Страница 55: ...e 39 Auto Answer Ring Count P249E Auto Answer Ring Count Value 0 99 Default 8 Page 46 Start of DTMF Remote Control Messages P250E Start of DTMF Remote Control Messages Value 0 99 Default 0 Page 45 Pro...

Страница 56: ...0 9999 Seconds Default 0 Page 25 Mains Fail Reporting Delay P319E Mains Fail Reporting Delay Value 0 9999 Seconds Default 600 Sec Page 46 Zone Contact ID Reporting Code P321E Contact ID Code for Zone...

Страница 57: ...unday 2 Monday etc Page 46 Programming Telephone Numbers P501E Programming Telephone Number 1 Value 1 16 Digits Page 38 P502E Programming Telephone Number 2 Value 1 16 Digits Page 38 P503E Programming...

Страница 58: ...rm 4 2 Code Default 89 Page 43 P533E Medical Alarm 4 2 Code Default 90 Page 43 Miscellaneous Alarm 4 2 Restore Codes P534E Panic Alarm Restore 4 2 Code Default 91 Page 43 P535E Fire Alarm Restore 4 2...

Страница 59: ...4E 4 2 Arm Code for Radio User 4 Default 64 Page 44 P565E 4 2 Arm Code for Radio User 5 Default 65 Page 44 P566E 4 2 Arm Code for Radio User 6 Default 66 Page 44 P567E 4 2 Arm Code for Radio User 7 De...

Страница 60: ...re Message for Zone 5 Default 35 Page 43 P596E 4 2 Bypass Restore Message for Zone 6 Default 36 Page 43 P597E 4 2 Bypass Restore Message for Zone 7 Default 37 Page 43 P598E 4 2 Bypass Restore Message...

Страница 61: ...to Factory Defaults P624E Restore Addresses 500 599 to Factory Defaults Page 34 Restore All Radio Zone Pendants to Factory Defaults P625E Restore All Radio Zone Pendants to Factory Defaults Page 34 C...

Страница 62: ...emote set 407 000 Command Control arm disarm Arm by Keyswitch 409 001 Area A Keyswitch Arm Disarm 409 002 Area B Keyswitch Arm Disarm Arm by Up Download 407 000 Remote PC arm disarm Radio key Panic 12...

Страница 63: ...nation with option 2 at P188E If full reporting of the part set alarm state Monitor Mode is required then option 2 7 will be turned on If alarms only are required for the part set mode then option 2 w...

Страница 64: ...by a non repetitive tone you can now fit a DTMF board to the panel and if fitted all domestic alarm reports will ONLY be kissed off by a valid DTMF tone By adding the DTMF board to the panel and leavi...

Страница 65: ...ease follow this table You must set the Report Option as describe in The table to Ensure Dialer operation correctly C S Central station C I D or 4 2 enario Report option comments Tel 1 C S Tel 2 C S B...

Отзывы: