Page 16
Option 6
Duress Alarm to Output
- This option will map the Duress Function to an output. Programming of
the Duress Digit is at address P230E.
Option 7
Mails Fail To Output
- A mains failure will be indicated at this output when option 7 is enabled at
this address. The Alarm Reset Timer must be set to “0”
when this option is used.
Option 8
Low Battery
- A battery Low condition will be indicated at this output when option 8 is enabled at
this address. The alarm reset timer must be set to “0” when this option is used.
P42E - P48E
As per P41E above for Outputs 2-8
MAPPING ZONE ALARMS TO OUTPUTS
ZONE ALARM MAPPING TO OUTPUTS - P51E - P58E
When a zone is in alarm (during the ARMED state only) this block of addresses allows individual
zones to be mapped to selected outputs. The default setting is that zones 1-8 will turn on all outputs
1-8 when in alarm.
P51E
Zone Alarms to Output #1. Options=Zones 1-8 (Default=
1-8)
P52E
Zone Alarms to Output #2. Options=Zones 1-8 (Default=
1-8
)
P53E
Zone Alarms to Output #3. Options=Zones 1-8 (Default= 0 )
P54E
Zone Alarms to Output #4. Options=Zones 1-8 (Default= 0 )
P55E
Zone Alarms to Output #5. Options=Zones 1-8 (Default= 0 )
P56E
Zone Alarms to Output #6. Options=Zones 1-8 (Default= 0 )
P57E
Zone Alarms to Output #7. Options=Zones 1-8 (Default= 0 )
P58E
Zone Alarms to Output #8. Options=Zones 1-8 (Default= 0 )
MAPPING STAY ZONE ALARMS TO OUTPUTS
STAY ZONE ALARM MAPPING TO OUTPUTS - P61E - P68E
When a Stay Mode zone is in alarm (during the STAY
state only) this block of addresses allows individual zones
to be mapped to selected outputs. The default setting
is that zones 1-8 will turn on output 2 only when a STAY
mode alarm occurs.
P61E
Stay Mode Zone Alarms to Output #1. Options=Zones 1-8 (Default=
1-8
)
P62E
Stay Mode Zone Alarms to Output #2. Options=Zones 1-8 (Default=
1-8
)
P63E
Stay Mode Zone Alarms to Output #3. Options=Zones 1-8 (Default=None)
P64E
Stay Mode Zone Alarms to Output #4. Options=Zones 1-8 (Default=None)
P65E
Stay Mode Zone Alarms to Output #5. Options=Zones 1-8 (Default=None)
P66E
Stay Mode Zone Alarms to Output #6. Options=Zones 1-8 (Default=None)
P67E
Stay Mode Zone Alarms to Output #7. Options=Zones 1-8 (Default=None)
P68E
Stay Mode Zone Alarms to Output #8. Options=Zones 1-8 (Default=None)
MAPPING 24 HOUR ZONE ALARMS TO OUTPUT
24 HOUR ZONE ALARM MAPPING TO OUTPUTS - P71E - P7
8E
When a 24 Hour zone is in alarm this block of addresses allows
individual zones to be mapped to selected outputs. The default
setting is that zones 1-8 will turn on output 2 only when a 24 Hour
alarm occurs.
P71E
24 Hour Zone Alarms to Output #1. Options=Zones 1-8 (Default=
1-8
)
P72E
24 Hour Zone Alarms to Output #2. Options=Zones 1-8 (Default=
1-8
)
P73E
24 Hour Zone Alarms to Output #3. Options=Zones 1-8 (Default=None)
P74E
24 Hour Zone Alarms to Output #4. Options=Zones 1-8 (Default=None)
P75E
24 Hour Zone Alarms to Output #5. Options=Zones 1-8 (Default=None)
P76E
24 Hour Zone Alarms to Output #6. Options=Zones 1-8 (Default=None)
1 2 3 4 5 6 7 8
Alarm To O/P 1
Stay Alarm O/P 1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
24 Alarm O/P 1