17
How to Add or Change Telephone Numbers
Your panel will accept up to 4 phone numbers with a total of 16 digits. Your panel can be
programmed to dial all or any of these depending on the event which has occurred.
(The 4
phone numbers are at program address 501 through to 504).
While in
CLIENT
mode, key in the following sequence
<PROGRAM> <501> <ENTER>
(The address for telephone number 1), The existing number will be flashed out at the
Keypad then enter
<NEW TELEPHONE #> <ENTER>
The new numbers will be flashed
back to confirm acceptance.
At any time you can enter in the address for the telephone number just to view the currently
programmed value then press the
<PROGRAM>
button to move on to another address.
Note
:
Address 501 = PH # 1, 502 = PH# 2 to 504 = PH# 4.
(Note: on the LED keypad “0” is indicated by LED “A” and “9” by LED “B”)
How to operate the access control output
If the alarm system has been set up to allow control of an electric door lock, you can
activate the door release function as follows;
Press
<CONTROL>
or Press
<CONTROL> enter CODE then <ENTER>
The Control LED will lights up while the lock is active and turn off as soon as power is
removed from the lock.
The Access Control function can either be a single button operation or restricted to
requiring a valid User code entry. Both options are shown above. Please consult your
installer as to what option may be programmed.
How to start Walk test Mode
While in
CLIENT
mode a User with the proper authority can start walk-test mode. This
special mode latches the alarm signals from detectors at the keypad initiating the test so
that one person can trigger every detector connected to the alarm then return to the
keypad to verify operation. On terminating Walk-test mode the test results are put into the
memory buffer
so they can be viewed at a later time.
To start Walk-test mode while in
CLIENT
mode press
<PROGRAM> <627> <ENTER>
The keypad buzzer will beep at 1-second intervals
Next trigger every detector connected to the panel then return to the keypad and all of the
zones that were triggered will be displayed at the keypad.
To terminate Walk-test mode press
<ENTER>
The keypad will stop beeping and automatically exit
CLIENT
mode.