Control System
Crestron
Lighting
Step 2: Module Selection
The enclosure mounted Crestron modules, connected to the appropriate terminal
block, perform pre-determined functions with various types of light sources, motors
and non-lighting loads. Modules have a Cresnet link for control processor
communication and a module override connection. Six different modules are
available. The type of load, number of circuits, required current load capacity, and
economic considerations are all determining factors when choosing modules. The
number and type of modules is determined from the load schedule. The number of
required modules will determine the size and type of enclosure(s) in the next step.
Each module is wired via the terminal block to a circuit breaker (provided by others).
The power provided to the module is distributed to all of its outputs. Each module
contains relays that provide an individual air gap for each controlled high voltage
circuit. Module selection can be done manually or by the D3 Pro software.
NOTE:
A module terminal block (CLT-Series device) must also be ordered for each
module. The corresponding CLT terminal block is installed in the enclosure for high
voltage wire termination. Each terminal block includes a terminal rail for mounting
the terminal block in the enclosure. Terminal rails and blocks do not occupy a
module space within an enclosure.
Oversized heat-sink fins on the face of the module provide superior heat dissipation,
eliminating heat related failures. The modules incorporate spit-bobbin transformers
and ground reference electronics for superior performance. AC line noise
interference and lamp flicker are eliminated by an innovative zero-crossing detection
technique and unique Crestron firmware. The red LEDs on the side of the module
indicate the presence of voltage to the module output. The brightness of the LED
corresponds to brightness of the lights. The green and amber Cresnet
communications LEDs indicate both power and communication.
Module Specifications
CLX-2DIM2
has two input feeds and two large capacity dimmers. This module
handles larger loads like chandeliers, landscape lights, and loads using many
transformers or 2-wire ballasts. Each output circuit is limited to 1920 watts (16A).
CLX-2DIM2 Module Specifications
Load Type
Incandescent, magnetic low-
voltage, neon and cold cathode
lighting, and 2-wire fluorescent
ballasts
Module Output
2 controlled circuits, 16A per
controlled circuit, 32A total
Heat Dissipation
170 BTU/Hr (with full load)
Terminal Block
CLT-2DIM2
Input Voltage
Two 120 VAC 60 Hz, single-
phase (same phase)
Size (H x W x D)
7 3/8 x 6 7/8 x 3
Temperature Range
32 – 104° F
Humidity Range
10 – 90% RH (non condensing)
Weight
3 lbs.
8
•
Lighting Control System Design
Design Guide – DOC. 5999A
Содержание Lighting Control System
Страница 1: ...Crestron Lighting Control System Design Guide ...
Страница 4: ......
Страница 40: ...Control System Crestron Lighting 36 Lighting Control System Design Design Guide DOC 5999A Module Wiring ...
Страница 41: ...Crestron Lighting Control System PAC2 Connections Design Guide DOC 5999A Lighting Control System Design 37 ...