Lighting
Derating
In a multi-gang installation, several dimmers are grouped in one horizontal wall box.
When this is the case, the inner heat sink section is removed to permit the installation
of a one-piece multi-gang wallplate. Removing the heat sink reduces the current
carrying capability of the dimmers due to reduced heat dissipation. The following
table provides the derating information for this application.
Application
No Heat Sink Removed
– Single Unit
One Heat Sink Removed
– Two Gang
Both Heat Sinks Removed
– Three or more Gang
Incandescent and Tungsten
Halogen
1000 W (800 W)
600 W (450 W)
400 W (300 W)
Magnetic Low Voltage
1000 VA / 750 W
(800 VA / 600 W)
600 VA / 450 W
(450VA / 300 W)
400 VA / 300 W
(300 VA / 200 W)
For additional installation information, refer to the CLW-DIM, DIMS & SLVD
Installation Guide (Doc. 5995).