Crestron
CLS-C6/C6M & CLSI-C6/C6M
iLux Integrated Lighting System
Operations Guide – DOC. 6347E
iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M
•
37
When the
Override
mode is disengaged, all loads revert to their previous values.
While in
Override
mode, all slave units are placed into
Override
mode as well,
regardless of the room combining status.
While in
Override
mode, all Cresnet commands (whether sent by a control
processor, or by a master iLux to a slave) shall be ignored, except for load level
commands, which cause the new final value to be stored and thus recalled when the
unit exits
Override
mode.
Override
mode levels take precedence over any limits set by
Load Shed
mode.
Load Shedding (Demand Response)
The iLux can enter a
Load Shed
mode via an external input (such as into a DIN-IO8
or GLS-SIM).
When entering
Load Shed
mode, any loads that must have their levels reduced shall
do so with a 1/2-second fade.
While in
Load Shed
mode, all loads must always be kept at or below their load shed
level (the only exception being
Override
mode).
When exiting
Load Shed
mode, loads that were commanded to go to a level below
their load shed level shall fade to the originally desired level in 1/2 seconds.
While in
Load Shed
mode, the 7-segment display shall flash "LS" at a rate of 1
second on, 1 second off, unless the display is actively showing something else.
Using iLux Designer, any value can be entered into the Load Shed Max field (0-
100%). The default Load Shed Max value in iLux Designer is 80% for all loads.
Building Management System (BMS) Interface
A DIN-IO8 unit is supported for the purpose of providing a contact-closure interface
to a Building Management System. A GLS-SIM is supported for the purpose of a
very basic contact-closure interface to a Building Management System.
The DIN-IO8 is required to have a designated Cresnet ID in order to work properly
in this capacity. The designated addresses are 0xD0 for normally open and 0xD1 for
normally closed DIN-IO8 types.
The functionality of the DIN-IO8 and/or GLS-SIM is fixed and cannot be changed
via
Setup
mode or iLux Designer.
The functionality provided by the DIN-IO8 is as shown in the following table:
DIN-IO8 BMS Functionality
PORT
FUNCTION
1
Recall On Scene (edge-triggered)
2
Recall Off Scene (edge-triggered)
3
Recall Scene 14 (edge-triggered)
4
Recall Scene 15 (edge-triggered)
5
Override
Mode (level-triggered)
6
Load Shed
Mode (level-triggered)
7
Defeat Occupancy. Sensors (level-triggered)
8
Lockout Front Controls (level-triggered)
Four unique Cresnet IDs are defined for the GLS-SIM to allow this unit access to the
following functions (2 per ID):·
•
Unit 1 (Cresnet ID 0xC5): Recall On/Off scene