Crestron
CLS-C6/C6M & CLSI-C6/C6M
iLux Integrated Lighting System
Operations Guide – DOC. 6347E
iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M
•
20
function front panel buttons to jump to a specific shade group.) The front
panel LED corresponding to the selected shade group lights.
•
While in
AS
mode, the bar graphs indicates the status of each of the six
shade groups: if no controllers are assigned, all LEDs remain off; if SDC
controller(s) are assigned, the bottom two LEDs light; if SDC-DC
controller(s) are assigned, the bottom three LEDs light; if SSC controller(s)
are assigned, the top two LEDs light.
•
When a given “AS / #” is displayed, press the channel 1 or channel 2 up or
down button on a shade controller to assign that channel of the shade
controller to the current group. When the button is pressed, the
Setup
LED
on that device flashes for 1 second to confirm that it has been assigned. The
bar graph for that group also flashes off for 1 second.
•
Go to a shade group and assign all channels. Then go to the next shade
group and assign those channels. Repeat for all shade groups.
NOTE:
A given shade group can only have one type of shade controller
(SDC, SDC-DC, or SSC). If a shade controller of a given type is assigned to
a group that already contains shade controllers of the other type, the other
controllers are removed from that group. Also, a given channel on a shade
controller can only belong to a single group. So if a shade controller that
belongs to one group is assigned to a new group, it is removed from the first
group. Therefore, if a shade controller is accidentally configured to the
wrong group go to the correct group and reassign it.
Once all shade controllers are assigned, press
Save
to save the assignments and
return to
Standard
mode, or press
Cancel
to discard the assignments.
Display/Set MNET ID Of This Unit (id)
If this unit is to be connected to a Cresnet control system network, change its MNET
ID. (When connected to another CLS-C6 unit’s local network do not set the ID –
running Auto Discovery on the master device does this automatically, as well as the
Set ID process of the iLux Designer.) To do this:
1.
Enter
Setup
mode and scroll to the “id” option, using the
^
and
v
buttons.
2.
Press the up/down button. The display shows the current MNET ID. The
id
mode is now locked. A dot is shown to the right of the “id.” The display
alternates between “id” and the current MNET ID.
3.
Use the up/down button to adjust the ID up or down (03-FE).
NOTE:
The valid address range is 03 – 20. If at any time the transceiver
connection is lost because the serial jack was inserted, the “E1” error code
is shown, the
Save
led turns off, and the
Cancel
led turns on. The Cancel
button can be used to exit
Setup
and enter
Standard
mode.
4.
If the button is held for more than 1/2 second, the unit auto-repeats and
starts scrolling through the values. At the upper or lower limit, the unit
pauses for 1/2 second and then wraps around.
5.
Press the
Save
button to save the new value and return to
Standard
mode.
Press the
Cancel
button to return to
Standard
mode without saving – the
current MNET ID is retained.
Error Code:
“E1” = Cannot communicate with transceiver.