Product Manual — Doc. 9096A
DIN-GWDL and DIN-GWDL-SPLTR • 21
Wiring
l
Use shielded CAT5 wire or better with a shielded connector.
l
DIN-GWDL connections:
o
Connect a light fixture daisy-chain or a DIN-GWDL-SPLTR to DMX 1 or DMX 2.
o
When using a DIN-GWDL-SPLTR, connect the DIN-GWDL-SPLTR directly to DMX 1
or DMX 2 on the DIN-GWDL.
l
DIN-GWDL-SPLTR connections:
o
Connect a light fixture daisy-chain to OUT 1, 2, 3, or 4.
o
Add the included 120Ω termination resistor to the DMX IN connector. The
termination resistor is preinstalled in an included terminal block.
o
Cascading DIN-GWDL-SPLTRs is not recommended.
l
Do not use more than 1,000 ft (305 m) of cable between a DIN-GWDL or DIN-GWDL-
SPLTR and the last light fixture in a daisy-chain. Do not use more than 1,000 ft (305 m) of
cable between a DIN-GWDL and a DIN-GWDL-SPLTR.
l
A light fixture daisy-chain must be terminated at end of the run. A termination is included
with each Crestron light fixture.
l
RJ-45 adapters are included with the DIN-GWDL and DIN-GWDL-SPLTR and should be
used for all DMX-C connections.
l
Do not connect CAT5 STP cables carrying DMX-C to Ethernet equipment.
l
Mark CAT5 STP cables carrying DMX-C.
l
Avoid long runs that are parallel with power cables
l
If the cable may come into contact with fixtures or other hot objects, use CAT5 STP cable
with an appropriate jacket.
l
DMX-C lines cannot be split using a splitter cable or Y adapter. Use a DIN-GWDL-SPLTR
instead.
l
If the CAT5 STP cabling may be repurposed in the future for an Ethernet network,
maintain cable lengths less than 328 ft (100 m). Longer CAT5 STP cable runs will not be
able to carry Ethernet data.
If an obstruction is preventing use of an RJ-45 adapter, do not directly connect solid CAT5 STP
cable to the 3-pin connector. Screw-down connectors may damage or weaken the wires.
l
To avoid obstructions:
o
In a DIN-EN-2X18, do not mount the DIN-GWDL or DIN-GWDL-SPLTR in the top
position.
o
Do not mount a DIN-GWDL-SPLTR directly above another DIN-GWDL-SPLTR.
Содержание DIN-GWDL
Страница 5: ...v Contents Product Manual Doc 9096A...
Страница 13: ...13 DIN GWDL and DIN GWDL SPLTR Product Manual Doc 9096A Dimension Drawings...
Страница 16: ...Product Manual Doc 9096A DIN GWDL and DIN GWDL SPLTR 16 Dimension Drawings...
Страница 39: ...This page is intentionally left blank Product Manual Doc 9096A DIN GWDL and DIN GWDL SPLTR 39...