Integrated Control System
Crestron
CNMSX
NOTE:
Not normally required, the
Make Permanent
button also creates a
permanent memory image.
6. After transferring the program file, click on the
Check Program
button
to ensure that the file loaded properly. The information in the
Current
Program
field of the "Cresnet Simpl Program" dialog box should update
and display the file currently loaded. If the information does not update,
repeat steps 3 through 5. If this does not remedy the problem, call
Crestron technical support. Refer to "Further Inquiries" on page 36.
Testing the Permanent Memory Image
Complete the following steps in the order provided to test the permanent memory
image.
1. Select
Tools | Viewport
to open the “Crestron Viewport” dialog box.
2. Unplug the CNMSX and leave it unplugged for about 10 seconds.
3. Plug the unit in and observe the statistics displayed in the Viewport
display field
. The program name uploaded into the system also appears.
4. Verify the displayed information against what was originally loaded
when the unit was shipped.
Loading Touchpanels
The CNMSX may include one or more touchpanels. Each panel must be set to the
proper network ID and loaded with a touchpanel
project
in order to work properly in
conjunction with the system program loaded in "Loading the System Program" on
page 29. For each panel in the system, a separate HEX file describing the graphical
elements of the panel is required. In some cases, where two or more panels are to be
identical in usage, a single HEX file may be used for multiple panels. To load a
touchpanel project into the panel, use the Crestron Viewport or the “Upload Project”
function in VisionTools™ Pro-e. For consistency, the steps that follow this paragraph
use the Viewport. To upload a HEX file into the touchpanel, complete the following
steps in the order provided.
1. Verify that the touchpanel is connected to the CNMSX via the
appropriate network cable. Also, verify that the touchpanel is set to the
proper network ID. (This info should be available in the system
connection sheets or directly from the programmer.)
2. Select
Tools | Viewport
to open the “Crestron Viewport” dialog box, if
it is not already opened.
3. Select
Diagnostics |
Report Network Devices
(alternatively, depress
F4) and verify that the touchpanel to be loaded reports back and is at the
expected network ID.
4. Select
File Transfer |
Send Touchpanel
(alternatively, depress
Alt+T
)
and set the network ID to the ID of the touchpanel to be loaded.
5. Browse for the supplied HEX file and click the
Open
button. The file is
sent to the CNMSX and then over the network to the touchpanel. Verify
that the panel displays a message saying that the upload is in progress.
30
•
Integrated Control System: CNMSX
Operations Guide - DOC. 8118B