The merchandiser is supplied with a service cord for the country of use and is terminated in a grounding type
plug. The wall receptacle used for this merchandiser must be properly polarized, grounded, and of the correct
voltage. Operating the merchandiser from a source of low voltage will
VOID YOUR WARRANTY
. Each mer-
chandiser should have its own electrical circuit and that circuit should be protected with a circuit breaker or
fuse conforming to local regulations.
Voltage Check -
Place the leads of a voltmeter across the LINE (LIVE) and NEUTRAL ter-
minals of the wall receptacle. The voltmeter should indicate 110-130 volts ac for 120 volt,
60 Hz locations, or 220- 240 volts ac for 230 volt, 50 Hz locations.
Polarity Check -
Place the leads of a voltmeter across the LINE (LIVE) and GROUND ter-
minals of the wall receptacle. The voltmeter should indicate 110-130 volts ac for 120 volt,
60 Hz locations, or 220- 240 volts ac for 230 volt, 50 Hz locations.
Noise Potential Check -
Place the test leads of a voltmeter across the NEUTRAL and
GROUND terminals of the wall receptacle. The meter should indicate 0 volts ac. A mea-
surement greater than 1.5 - 2.0 volts ac could result in problems for the merchandiser' s
electronic circuitry caused by electrical noise.
Any deviation from these requirements could result in unreliable performance from your merchandiser.