40
Table 4-3 Protection Parameters Table
No.
LCD indication
Description
Setup range (lower
limit, default &
upper limit)
1.
GridV.Max(V)
Grid voltage upper limit
(
200, 528, 533V
)
2.
GridVmaxTripT(S)
Trip time under Max. Grid V.
(0.05, 1.80, 2.00S)
3.
GridV.Min(V)
Grid voltage lower limit
(
0, 422, 480V
)
4.
GridVminTripT(S)
Trip time under Min. Grid V.
(
0.05
,
1.80
,
2.00S
)
5.
GridF.Max(Hz)
Grid frequency upper limit
(50.00
,
60.50
,
65.00Hz)
6.
GridF.Min(Hz)
Grid frequency lower limit
(45.00
,
59.30
,
60.00Hz)
7.
GridFTripT(S)
Trip time under Min. Grid F.
(
0.05
,
0.08
,
300.00S
)
8.
IsoResis(KOhm)
Insulation impedance lower
limit
(200
,
600
,
1200KΩ)
9.
ActivePower(%)
Active power derating
(
80.0%
,
100.0%
,
100.0%
)
10.
PowerFactor
Reactive power
compensation
(
-0.900
,
1.000
,
0.900
)
INSTRUCTION:
The function of
active power derating
and
reactive power
compensation
is optional. For detailed information, you may call our
after-sales service center.