Table 3-4 Wiring requirement
4 strings
6 strings
7 strings
8 strings
Positive
14~10AWG
16~10AWG
16~10AWG
18~10AWG
Negative 14~10AWG
16~10AWG
16~10AWG
18~10AWG
Bolts
M5
Torque
value
1.19N-M (10.5Lb-In.)
Note 1
:
The DC fuse protectors of different fusing capacity should be
chosen according to the short circuit current of PV modules. The
600VDC Littelfuse KLKD fuse series are recommended. The detailed
information is available for customers to find and download from
The recommended fuse types are listed in the following table:
Table 3-5 Recommended fuse types
DC input
2 strings/MPPT 3 strings/MPPT
4 strings/MPPT
Fuse
KLKD 30
KLKD 15
KLKD 15
Note 2: Concerning the current share of fuse for each DC input string, 1
or 2 DC input strings are NOT recommended. If it has to be, we suggest
that the DC input wire be connected to the inverter without DC fuses as
follows:
Содержание SC Series
Страница 1: ...CPS SC Series Grid tied PV Inverter CPS SC20KTL DO US 480 Installation and Operation Manual Ver 1 2 ...
Страница 17: ...15 Figure 3 7a Mounting inverter on the bracket Figure 3 7b Mounting inverter on the bracket Hand Grab ...
Страница 18: ...16 Figure 3 7c Mounting inverter on the bracket Figure 3 7d Mounting inverter on the bracket ...
Страница 30: ...28 Figure 3 21 Diagram of communication wiring ...
Страница 61: ...59 Figure 6 13 Securing panels on both sides ...