10.1
Series operation
■
Series operation is not possible.
10.2
Parallel operation
1)The basic note
■
Parallel operation is not possible BRFS30/40/60S
*1
.
*1 BRFS40/60S has a parallel option "P".
■
Parallel operation is impossible different series.
■
Total number of units should be no more than 5 pieces.
■
Rating output current at parallel operation
= Rating current per unit × number of unit ×0.9
2)Wiring
■
The wiring of the parallel operation in Fig10.2.1.
■
TRM terminal of slave should be connect to GND(100Ω or less) .
■
Sensing terminal of the slave to open.
■
Connect all SHARE terminal.
■
When controlling the rise time by SEQ is possible to connect all SEQ pin.
■
RC terminal of the slave to connected GND or connect to the master of the
RC terminal.
■
Input power should be supplied from the same power supply.
■
BRFS40-P and BRDS40 is required inductance of more than 0.1uH to the Vin line.
Fig. 10.2.1
Example of wiring
method in parallel
operation
BRFS/BRDS 10-1
10. Series operation / Parallel operation
Applications manual
For BRFS/BRDS series